First, the conclusion:Curtain-wall anti-fall systems are not applied on a blanket basis according to "how many metres tall the building is"; rather,if any of the three conditions is met, installation is mandatory: first, the building or curtain-wall height exceeds limits, or panel dimensions and weight are excessive; second, the location is a densely occupied area, an entrance/exit, or above a walkway; third, brittle panels are used with non-through-fastening connections (back bolts, short slots, slotted pendants). When all three conditions overlap, the system must alsoindependent of the main load-bearing connectionas a secondary restraint, rather than adding a "spare nut" to the main connection.
Scope of application:This article discusses theanti-fall construction details, focusing on the secondary restraint between the panel and the main structure; it applies to the design, detailed design, and construction of new and retrofit curtain walls. It does not cover periodic safety inspection procedures for existing curtain walls, nor the details of the heat-soaking process for glass spontaneous breakage, nor does it replace structural calculations for specific projects. Dimensions and thresholds in this article are commonly used engineering control values; the current code provisions and design documents govern in the final analysis.
Regarding anti-fall systems, the two most entrenched misconceptions in the industry are 'only needed for high-rise' and 'no need if back bolts are installed'. The flaw in the former is this: a stone panel falling onto a commercial street sidewalk and one falling onto a 30th-floor rooftop equipment platform have completely different consequences—what determines the risk is not the height, but what lies beneath the fall point. The flaw in the latter is: back bolts address 'how the panel is fixed', while anti-fall systems address 'what happens after the fixing fails'—these are problems at two different levels, and however well the back bolts are done, they cannot replace the latter.
There is another, less obvious misconception: understanding anti-fall as simply "adding a wire rope". In fact, the core of an anti-fall system is not the rope, butthe reliability of the connections at both ends, the amount of displacement it allows, and whether it is independent of the main load path. A wire rope fixed to the same already-failed pendant serves no purpose whatsoever.
1. What the code requirements actually point to
1.1 Three things the code cares about
The anti-fall requirements in the current system of curtain-wall codes (glass curtain walls, metal and stone curtain walls, general technical conditions for building curtain walls, etc.) can be summarized in three levels:
Panels must not fall and injure people.This is an objective requirement and the starting point for all construction measures. The code does not prescribe "which product must be used"; instead, it requires that in areas with dense pedestrian traffic or at significant heights, panels must not fall freely even if they become detached from the main connection.
Connections should have a reliable secondary restraint.For brittle panels and non-through-fastening connections, the code requires construction measures to prevent panels from falling. Such measures must beindependent load path, and must not share the same potentially failing node with the main connection.
Materials and corrosion protection should meet the design service life.Anti-fall components remain in concealed locations for long periods and are difficult to maintain; their corrosion-protection rating should not be lower than that of the panel connectors, and connections must not create galvanic corrosion.
1.2 Why the code gives "conditions" rather than "height figures"
Because risk is a function of four variables: height, panel mass, landing-point environment, and connection type. At the same height of 20 m, a 0.5 m² thin ceramic panel and a 2.5 m² thick stone panel differ several-fold in fall energy; and the same panel falling on a green belt versus at the gate of a primary school has completely different consequences. By using a "condition-triggered" approach, the code leaves the judgement to design and review, which also meansyou cannot escape responsibility by relying on a single figure。
2. Trigger condition 1: Height and panel dimensions
Table 1 Combined assessment of height and panel dimensions (commonly used engineering control values)
| Building/curtain-wall height | Area of a single panel | Anti-fall requirement | Remarks |
|---|---|---|---|
| ≤ 24 m (multi-storey) | ≤ 1.0 ㎡ | According to conventional details; still required where the landing point is a pedestrian walkway | Risk is governed by the landing-point environment rather than height |
| 24–50 m | 1.0–1.5 ㎡ | should be provided with a secondary restraint | Large panels have high inertia; failure of a single point causes the entire panel to fall |
| 50–100 m | ≥ 1.2 m² or excessive single-panel mass | should be installed | High wind pressure and difficult maintenance require a systematic design |
| > 100 m (super-tall) | Any size | must be installed | Both fall energy and maintenance cost are unacceptable |
| Any height | ≥ 1.5 m² or overweight panels | must be installed | Single-panel mass is large, leaving no possibility of manual intervention |
This table should be read together with a cautionary reminder:curtain walls below 24 m may likewise require installation. The three-storey podium of a commercial complex, a metro entrance, or a school covered walkway may have a curtain wall only ten-odd metres high, but the landing point is a busy pedestrian route, so the risk level is no lower than that of a high-rise. In assessment, consider the landing point first and the height second.
3. Trigger condition 2: Dense occupancy and entrances/exits
3.1 Five types of locations that must be treated as "densely occupied"
Above the main entrances/exits and lobbies of buildings.These are the highest-risk points: people remain there for long periods, at high density, and often with no cover. Curtain-wall panels above entrances/exits should be provided with a secondary restraint regardless of height.
Under and beside pedestrian walkways, covered walkways, and footbridges.Including passageways formed by building setback lines, elevated open floors, and weather-protected covered walkways. These locations are characterized by people "passing through" rather than "lingering", but the throughput is high and the cumulative exposure time is long.
Commercial streets, plazas, schools, hospitals, and stations.What these places have in common isuncontrolled crowds— elderly people, children, and those with limited mobility, whose risk cannot be reduced through management measures.
Above underground garage entrance ramps and around sunken courtyards.Often overlooked because they are not on the main façade, but the landing point is likewise an area used by pedestrians.
Fire-fighting and rescue areas and elevated operation platforms.People are active in these areas in emergencies, and codes usually specify clear-headroom and safety requirements; curtain-wall construction must not create a falling hazard.
3.2 Assessment method: Draw a "vertical projection line"
The simplest practical assessment method is to project each section of curtain wallvertically onto the ground planon the site plan and see what lies within the projected area. If it is landscaping, a roof, or an equipment platform, the risk is manageable; if it is hard paving, a walkway, parking spaces, or a children's play area, treat it as densely occupied. This method requires no complex calculation but can identify all "missed" locations in one pass, making it especially suitable for rapid screening at the concept stage.
4. Trigger condition 3: Panel and connection type
This is the most easily overlooked and also the most technical condition. The need for anti-fall protection is directly related to "whether the whole panel will fall once it detaches from the main connection", which depends on the nature of the panel and the connection method.
Table 2 Anti-fall necessity corresponding to panel and connection types
| Panel | Connection type | Behaviour after detachment | Necessity of anti-fall protection |
|---|---|---|---|
| Stone, ceramic panels, sintered stone | Back bolt (non-through-fastening) | Whole panel falls freely, with no restraint | High; installation mandatory |
| Stone, ceramic panels | Short-slot and slotted pendants | Whole panel falls after the slot edge breaks out | High; installation mandatory |
| Stone | Through-fastening pins / dowels | Does not fall as a whole while the pins remain connected | Medium; judge according to height and landing point |
| Glass | Laminated insulating glass, point-supported | After breakage, held by the interlayer film; the whole pane may come out of the frame | High; secondary restraint especially needed for point-supported glazing |
| Aluminium panels, aluminium composite panels | Folded edges with pendants / spacers | Light weight; edges often remain hanging | Medium; focus on stiffeners and pendant anti-disengagement |
| Any panel material | Back bolts + only a single fixing point (fewer than 4 points) | Failure of the single point means instability, with possible overturning and detachment | High, and the number of connection points should be corrected first |
The key to reading this table is one keyword:non-through-fastening. Back bolts, short slots, and slotted pendants are all connections that 'bear load only locally at the back or edge of the panel'; once that local area fails, there is no mechanical link at all between the panel and the main structure. Through-fastening connections (pins and dowels passing through the panel thickness) often retain some residual connection after failure, giving a lower probability of falling. Therefore the main beneficiaries of anti-fall systems are precisely today's most mainstream back-bolt curtain walls.
Another point that needs clarification:the quality of the back bolt itself cannot replace an anti-fall system. However well a back bolt is made, it addresses 'not detaching under normal load'; the anti-fall system addresses 'not falling under abnormal conditions (back bolt failure, panel cracking, seismic displacement, strength degradation after fire)'. The two are in series, not substitutes.
5. Comparison of three system types
Table 3 Comparison of three anti-fall system types
| Type | Construction detail | Advantages | Limitations | Applicability |
|---|---|---|---|---|
| Wire rope type | Stainless steel wire rope passes through pre-drilled holes in the back of the panel or dedicated connectors, with both ends anchored to the main structure, forming a continuous restraint | Good flexibility, accommodates displacement, continues to transfer load after a single point fails, relatively low cost | Requires control of tension and sag; rope-end anchorage quality determines success; appearance must be concealed | Large-area regular curtain walls, super-tall buildings |
| Support plate / hook type | Add stainless steel support plates or anti-disengagement hooks to the pendant system, supporting the panel bottom or hooking the panel edge | Simple construction, straightforward installation, easy maintenance, integrated with pendants | Depends on contact between the support plate and the panel; may fail under large displacement; requires adequate panel edge strength | Mid- and low-rise buildings, podiums, accessible maintenance areas |
| Independent anchor point + connector type | Each panel has an independent anti-fall connector, with one end fixed to a dedicated hole in the back of the panel and the other end anchored independently to the structure (not sharing anchors with the main pendant) | Completely independent load path, allows single-panel replacement, highest reliability | Increased steel usage and number of anchor points, highest cost, high demands on structural provision | Super-tall buildings, large panels, areas above entrances/exits, and key public buildings |
The three forms are not ranked as "good, fair, poor"; they are matched according to risk level and feasibility. The wire-rope type is the best overall for large-area curtain walls on super-tall buildings, because a single continuous restraint covers the entire area — even if a local pendant fails, the panel remains "strung" on the rope. The bracket type has the advantage of being simple and intuitive, suitable for locations with few floors where close-range inspection and maintenance are possible. The individual anchorage-point type is the most expensive, but it is the only form that can ensure "the failure of one panel does not affect adjacent panels", so it is worth using above entrances/exits and where individual panels are heavy.
Common in engineering practiceCombined use: Use the wire-rope type on typical floors, individual anchorage points at entrances/exits and for large panels on the first floor, and the bracket type at low levels of the podium. This zoning strategy is more economical than using a single form throughout the building and better matches the distribution of risk.
6. Connection details with the back bolt system
Table 4 Connection details between the anti-fall system and back bolts
| Connection location | Key points of the method | Load path | Common errors |
|---|---|---|---|
| Dedicated anti-fall hole on the back of the panel | Provide a separate blind hole on the back of the panel (not shared with the main back bolt hole) for the anti-fall connector | Panel → anti-fall component → rope/rod → structure | Hanging directly on the main back bolt is equivalent to having no secondary protection |
| Pendant body | The anti-fall component is mechanically connected to the pendant, but has an independent anchorage point | Panel → pendant → anti-fall component → structure | The anti-fall component and the pendant share the same anchor |
| Anchorage to the main structure | Independent anchor or cast-in insert, located away from the main pendant anchorage zone | Carries load independently, without interfering with the main connection | Anchored into masonry, plaster, or thin panels |
| Displacement coordination | Reserve sufficient free travel so that no load is carried under normal conditions | Carries load only when the main connection fails | Over-tensioning, causing it to carry load at all times and form a rigid restraint |
| Corrosion protection and isolation | Insert insulating pads between stainless steel and aluminium components to avoid galvanic corrosion | — | Stainless steel in direct contact with an aluminium pendant causes corrosion of the aluminium under prolonged damp conditions |
The single most important principle in connection design is:The anchorage points of the anti-fall system must be independent. If the anti-fall component is hung on the main back bolt, then when the main back bolt fails the anti-fall component fails at the same time; the same applies if the anti-fall component shares an anchor with the pendant. A truly effective secondary restraint follows a path from panel to structure thatshares no failure element whatsoeverwith the main connection.
The second key point isdoes not carry load under normal conditions. Under normal service conditions, the anti-fall system should remain in a "standby" state, allowing a certain amount of displacement without being tensioned. If it is over-tensioned during installation, it will share wind loads and thermal deformation with the main connection, remaining at high stress over the long term and potentially suffering fatigue failure first.
7. Six control points for design and construction
Control point 1: Draw the projection lines first, then determine the form.Complete the landing-point analysis during the concept stage and produce an "anti-fall zoning plan", so that nothing has to be added hastily during the construction-document stage.
Control point 2: Reserve independent holes on the back of the panels.Anti-fall holes should be reserved during panel fabrication; drilling on site damages the panel and makes it difficult to ensure the quality of the hole bottom. Hole diameter and depth should be controlled according to the anti-fall component parameter table.
Control point 3: Verify structural-side anchorage by pull-out testing.There are many anti-fall anchorage points and each carries a modest load, but failure of one means failure of the system; batch sampling inspection should be carried out.
Control point 4: Control tension and free travel.The wire-rope type should have explicit sag or tension requirements; the bracket type should maintain a reasonable clearance from the underside of the panel to avoid hard contact.
Control point 5: Corrosion protection and galvanic isolation.Provide insulating pads at contact points between stainless steel and aluminium or galvanized components; concealed areas should be configured with a corrosion-protection rating no lower than that of the main connecting components.
Control point 6: Retain images of concealed-work inspection.Once installed, the anti-fall system is usually concealed by panels and finish layers; inspection must be completed before enclosure, with images and records retained and included in the as-built documentation.
8. Common misconceptions: Five practices that render the system ineffective
Misconception 1: Hanging the anti-fall wire rope on the main back bolt.Symptom: For convenience, the rope is looped directly around the tail of the back bolt. Consequence: when the main back bolt fails, the rope falls with it and the secondary protection fails completely. Correct approach:provide a dedicated anti-fall hole and an independent connector on the back of the panel, with an anchorage point independent of the main connection.
Misconception 2: Installing the system only on high-rise areas, not on the podium or at entrances/exits.Symptom: A blanket height-based approach, with no anti-fall protection for large panels on the first floor. Consequence: the landing point is precisely where pedestrian traffic is heaviest, so the risk is highest. Correct approach: judge according to Table 1 and the projection lines in this article;the landing point takes precedence over height。
Misconception 3: Pulling the rope taut and straight during installation.Symptom: Believing that "the tighter, the safer". Consequence: the anti-fall system carries load at all times and deforms together with the main connection; prolonged high stress may cause fatigue of the rope-end anchorage or local crushing of the panel. Correct approach: retain a reasonablefree travel, so that it carries load only when the main connection fails.
Misconception 4: Placing anti-fall anchorage points in masonry or plaster.Symptom: No suitable location can be found on the structural side, so the anchor is simply fixed into an infill wall. Consequence: masonry has very low strength and the anchor pulls straight out under the impact of a fall, which is no better than doing nothing. Correct approach: anchor intoconcrete structure or reliable cast-in inserts, located away from the main pendant anchorage zone and verified by pull-out testing.
Misconception 5: Believing that anti-fall protection is unnecessary when back bolts are used.Symptom: Treating the load capacity of back bolts as a safety guarantee. Consequence: under abnormal conditions such as back-bolt failure, panel cracking, or seismic displacement, there is no restraint at all and the entire panel falls. Correct approach: make it clear that back bolts addressnormal load conditions, while the anti-fall system addressesabnormal conditions as a backup, with the two arranged in series.
9. Daring anti-fall system product support
The Daring panel anti-fall system is designed on the principle of "independent restraint". It works together with the back bolt system but does not share a load path, and can be used on super-tall curtain walls and large-panel areas, providing dual protection with back bolts carrying the main load and the anti-fall system as the backup.
Table 5 Daring anti-fall system configuration
| Item | Configuration and description |
|---|---|
| System composition | Stainless steel wire rope / anti-fall connector + dedicated connector on the back of the panel + independent anchor on the structural side |
| Material | 304/316L stainless steel, selected according to the corrosive environment |
| Applicable panels | Stone, ceramic panels, sintered stone, microcrystalline stone, and other back-bolt curtain-wall panels |
| Relationship with back bolts | Used in conjunction, with an independent load path and no shared main back-bolt anchorage points |
| Certification and testing | Mechanical property test and corrosion test data are provided according to the product system; parameters are subject to the type test report |
| Supporting tools | Back bolt drilling machine, dedicated drill bits, hole gauge, torque wrench, rope-end crimping tool |
| Documentation | Quality warranty, test reports, and certificates of conformity, which can be included in the as-built documentation for traceability |
10. Frequently asked questions
| No. | Question and answer |
|---|---|
| Q1 | How high must a curtain wall be before anti-fall protection is required? There is no single height threshold. In engineering practice, a reference line of "should be installed" is usually taken at over 50 m or a single panel area exceeding 1.2 m²; over 100 m or a single panel exceeding 1.5 m² is treated as "must be installed". However, where the landing point is a pedestrian walkway or entrance/exit, installation is mandatory even at low levels. |
| Q2 | Is an anti-fall system still needed when back bolts are used? Yes. Back bolts ensure that panels do not fall under normal load conditions, while the anti-fall system provides a second restraint under abnormal conditions such as back-bolt failure, panel cracking, or seismic displacement. The two are arranged in series and cannot replace each other. |
| Q3 | Can the anti-fall wire rope be fixed to the back bolt? No. Fixing it to the main back bolt means sharing the same failure point; once the back bolt fails, the anti-fall system fails at the same time. The correct approach is to provide a separate anti-fall hole on the back of the panel and an independent anchorage point on the structural side. |
| Q4 | Does the anti-fall system carry load under normal conditions? Under normal service conditions it should not carry the main load; a reasonable free travel should be reserved, and restraint of the panel should begin only when the main connection fails. Over-tensioning during installation keeps it at high stress over the long term, increasing the risk of fatigue and local crushing of the panel. |
| Q5 | Can an anti-fall system be retrofitted to an existing curtain wall? Yes, but it is more difficult than in new construction. It requires opening new anti-fall holes on the back of the panels (the panels are already installed, so drilling space is limited), adding independent anchorage points on the structural side, and carrying out pull-out verification panel by panel. Before modification, the remaining strength of the panels and the condition of the back bolts should be assessed. |
| Q6 | What is inspected during acceptance of an anti-fall system? Four items: pull-out records of the anchorage points, the quality of connections and rope-end crimping, whether free travel and tension comply with the design, and whether image documentation of concealed areas is complete. Since the system is concealed as soon as installation is complete, inspection before enclosure is the only opportunity. |
Ultimately, the decision on whether anti-fall protection is needed comes down to one question:what would this panel hit if it fell. Falling on a green belt and falling on a sidewalk are two entirely different engineering problems; and wherever it falls, as long as a non-through-fastening connection such as a back bolt is used, the panel has no restraint at all once it detaches from the main connection — this is precisely the reason anti-fall systems exist. It is not "extra insurance" for the back bolt, but a "way out" for the building.
The Daring panel anti-fall system is designed to work with the back bolt system, with an independent load path. It can provide secondary protection for super-tall and large-panel curtain walls, and comes with complete test data and supporting tools. For anti-fall zoning and connection detailing tailored to project height, panel dimensions, and landing-point conditions, please consult the Daring technical team.
References
JGJ 133-2013 Technical Code for Engineering of Metal and Stone Curtain Walls — Connection details and anti-fall requirements for stone panels
JGJ 102-2003 Technical Code for Engineering of Glass Curtain Walls — Provisions for panel connections and anti-detachment details
GB/T 21086-2007 Building Curtain Walls — General provisions for curtain-wall performance requirements and connection details
JGJ 339-2015 Code for Seismic Design of Non-structural Components — Seismic and anti-fall requirements for non-structural components such as curtain walls