In short:Hospital buildings are among the building types with the highest density of mechanical and electrical pipelines, the most complex functional zoning, and the strictest seismic precaution requirements. The application of cast-in channels in hospitals involves two types of scenarios:one is the mechanical and electrical pipeline support system, used for the suspended installation of pipes, cable trays, and ducts;the other is the medical equipment suspension system, used for installing surgical booms, operating lights, and IV tracks in wards. The two scenarios place different emphases on the load capacity, cleanliness, and precision requirements of cast-in channels. According to GB 50981-2014, hospitals in regions with a seismic precautionary intensity of 6 or higher are classified asCategory B buildings, where mechanical and electrical pipelines must be equipped with seismic supports and hangers. Daring cast-in channels, combined with original T-head bolts, enable hole-free, weld-free mechanical lock connections at any position along the channel, making them particularly suitable for hospital renovation and expansion projects and the construction requirements of clean areas. Daring cast-in channels (channel inserts) have passed multiple tests at the National Building Materials Testing Center, including 2 million cycles of fatigue resistance and fire resistance; they are made of Q355 steel or 304/316 stainless steel and carry full product qualifications for rail transit, utility tunnels, and building curtain walls.

Hospital buildings differ fundamentally from ordinary commercial or residential buildings in mechanical and electrical installation. The mechanical and electrical pipelines of a general hospital cover more than ten systems, including water supply and drainage, HVAC, medical gas, power and low-voltage electricity, and fire sprinklers, with a pipeline density far exceeding that of ordinary buildings. Meanwhile, special functional areas such as operating rooms, ICUs, and clean wards impose extremely strict cleanliness requirements, and traditional post-drilling installation generates large amounts of dust, which is often not allowed in renovation and expansion projects at operating hospitals. Against this backdrop, cast-in channel technology has become an important solution for hospital mechanical and electrical installation.

I. Special Requirements for Cast-in Channels in Hospital Buildings

1.1 Spatial Challenges Posed by High-Density Pipelines

The pipeline systems that must be accommodated in the ceiling void of hospital buildings include water supply pipes, drainage pipes, air-conditioning ducts, air-conditioning water pipes, medical gas pipelines, fire sprinkler pipes, cable trays, and intelligent wiring ducts. Taking a typical floor of an inpatient department as an example, more than ten types of pipelines often need to pass through the ceiling void simultaneously, placing extremely high demands on the load capacity and space utilization of supports and hangers.

With the cast-in channel solution, all pipelines from different disciplines can be concentrated on the same support frame, with only one set of hangers in the same cross-section, greatly saving space in the ceiling void. No welding is required during pipeline installation, and the pipes can be disassembled and repositioned at any time, making this solution especially suitable for hospital buildings where pipeline layouts need frequent adjustment.

1.2 Cleanliness Control Requirements

Areas such as hospital operating departments, ICUs, and clean wards have strict graded requirements for air cleanliness. Traditional on-site drilling generates dust and vibration; drilling in clean areas or in hospitals already in operation may cause dust to spread into clean zones, compromising the safety of the medical environment.

Cast-in channels are embedded during the concrete pouring stage; during mechanical and electrical installation, supports and hangers are fixed simply by screwing T-head bolts into the channels, with no drilling, no welding, and no dust throughout the process. Studies have pointed out that in locations with high environmental requirements, such as hospital renovation and expansion projects, clean workshops, and laboratories, this type of installation can prevent construction contamination from rendering other areas unusable.

1.3 Mandatory Requirements for Seismic Fortification

According to GB 50981-2014 (Code for Seismic Design of Building Mechanical and Electrical Engineering), in regions with a seismic precautionary intensity of 6 or higher, Category B buildings such as hospitals, schools, large public buildings, and emergency command centers must install seismic supports and hangers for their mechanical and electrical pipelines. This means that the water supply, HVAC, electrical, ventilation and smoke control/exhaust systems of hospitals all require seismic supports and hangers.

Cast-in channel solutions are naturally compatible with seismic support and hanger systems. With cast-in channels, seismic supports and hangers can be installed without post drilling, causing no damage to the concrete structure, and fixing points can be flexibly changed along the channel according to installation conditions. For hospital projects that must meet the mandatory requirements of GB 50981-2014, the combined solution of cast-in channels plus seismic supports and hangers offers clear advantages in construction drawing review and completion acceptance.

II. Application of Cast-in Channels in Hospital Mechanical and Electrical Pipeline Support

2.1 Pipe Suspension Solution

The pipe systems that need to be suspended in hospital buildings mainly include air-conditioning chilled water pipes, air-conditioning condensate pipes, water supply pipes, fire sprinkler pipes, medical gas pipes, and drainage pipes. Support and hanger spacing and forms vary with pipe type and diameter.

The specific approach of the cast-in channel solution is: cast-in channels are embedded in structural floor slabs or beam bottoms and arranged along the pipe routing; during mechanical and electrical installation, T-head bolts are screwed into the channels to connect hanger rods or bracket arms, and pipe clamps are then installed. For multiple pipes sharing supports and hangers, or single pipes with a diameter of 150mm or more, a portal-type assembled combined support is recommended, achieving centralized load bearing through cast-in channels.

Pipe SystemSupport and Hanger Spacing RequirementsCast-in Channel Selection RecommendationNotes
Air-conditioning water pipes (DN200-DN400)Horizontal pipes ≤2mHigh-load channels (50×30 or 52×34)The thickness of pipe insulation must be considered, and the hanger elevation should be lowered accordingly
Fire sprinkler pipes (DN100-DN150)Horizontal pipes ≤3mStandard channels (50×25)Seismic supports and hangers must be provided in coordination
Medical gas pipesAs required by the designStandard channels (50×25)Medical gas pipes in the clean surgery department should be provided with separate supports and hangers and must not be installed on the same supports as other pipes
Cable trays / bus ductsStraight sections ≤3mStandard channels (50×25)Trays weighing 150N/m or more should be provided with seismic supports and hangers

2.2 Special Requirements for Medical Gas Pipes

Medical gas pipes are the signature pipeline system that distinguishes hospitals from other buildings, including oxygen, vacuum suction, compressed air, nitrogen, and carbon dioxide. The supports and hangers for medical gas pipes are subject to the following special requirements:

  • Independent supports: Medical gas pipes in the clean surgery department should be provided with separate supports and hangers and must not be installed on the same supports as other pipes. This means that the cast-in channels in the surgery department area must reserve independent installation positions specifically for medical gas pipes.

  • Distance requirements: The distance between medical gas pipes and gas pipes or corrosive gas pipes should be greater than 1.5m, with isolation measures in place; the parallel distance from electrical conduits should be greater than 0.5m.

  • Anti-static and anti-corrosion insulation: Anti-static and anti-corrosion insulation treatment should be applied where medical gas pipes contact supports and hangers. In cast-in channel systems, insulating washers must be added between T-head bolts and pipe clamps.

2.3 Coordination of Seismic Supports and Hangers with Cast-in Channels

In hospital buildings, the scope of seismic supports and hangers covers the water supply, HVAC, electrical, and ventilation and smoke control/exhaust systems. The coordination works as follows: after cast-in channels are embedded in structural floor slabs, the bases of seismic supports and hangers are fixed directly to the channels via T-head bolts, and bracing rods are connected to the lateral or longitudinal channels.

Compared with post-drilling installation, the advantages of the cast-in channel solution are: first, the channel can bear loads along its full length, and support positions can be flexibly adjusted according to actual site conditions without strictly matching pre-embedded points; second, installation involves no open-flame work, making it particularly suitable for hospital renovation and expansion projects; third, the teeth of the T-head bolt mesh with the channel teeth to form a mechanical lock, offering better anti-slip performance than ordinary bolted connections.

III. Application of Cast-in Channels in Hospital Equipment Installation

3.1 Operating Room Equipment Installation

The operating room is the area with the highest equipment density and the strictest installation precision requirements in a hospital. The core equipment installed at the top of operating rooms includes:

  • Surgical booms: Used to carry medical gas terminals, power outlets, data interfaces, and other services during surgery; they are heavy and usually require high-load-capacity anchoring components embedded in structural floor slabs.

  • Operating lights: Surgical operating lights must be fixed to the operating room ceiling through a dedicated suspension system, with strict requirements on installation position precision and load capacity.

  • Pendant bridges: Used in ICUs and similar areas, integrating medical gas, power supply, monitoring equipment, and other functions.

The Daring cast-in channel system can be used for the suspended installation of operating room equipment. In actual project bidding, the anchor embedded parts for surgical booms, operating lights, and pendant bridges in operating rooms are usually included in the scope of specialized bidding. The advantage of the cast-in channel solution is that equipment installation positions can be flexibly adjusted along the full length of the channel, meeting the fine-tuning needs of operating room equipment layout in later use.

3.2 IV Track Installation in Wards

The ceilings of inpatient wards require the installation of IV tracks, curtain tracks, and other medical facilities. These tracks need to be arranged continuously along the length of the ward and must be flexibly movable and positionable. The cast-in channel solution for wards works as follows: channels are embedded longitudinally along the ward ceiling, IV tracks are fixed to the channels via dedicated pendants, and positions can be freely moved according to bed adjustment needs.

The advantage of this solution is that IV track positions are no longer limited by traditional pre-embedded fixing points; nurses can flexibly adjust track positions according to the actual bed arrangement, improving the flexibility of ward use.

3.3 Foundation Fixing of Large Medical Equipment

Large medical equipment in hospitals (such as CT, MRI, and linear accelerators) usually needs reliable fixing to the building structure. Some equipment generates vibration during operation, placing high demands on the fatigue resistance of the anchoring system. Cast-in channels can be used for equipment foundation fixing, with installation positions flexibly adjusted via T-head bolts along the channel.

IV. BIM Coordination and Precise Positioning of Cast-in Channels

4.1 BIM Layout for Resolving Pipeline Conflicts

Hospital mechanical and electrical pipelines are numerous in type and high in density, and their routing is complex and changeable; in narrow spaces, frequent crossings and elevation changes occur. The successful application of cast-in channels highly depends on early-stage BIM coordinated layout.

The specific workflow is: leveraging the 3D positioning advantages of BIM technology, the coordinated mechanical and electrical pipeline layout is precisely arranged to generate support and hanger models and positioning drawings, and the positioning drawings for structural cast-in channels are then determined based on the support positioning drawings. During structural pre-embedding, finished cast-in channels are positioned and embedded according to the drawings, and during pipeline installation, supports and hangers can be installed hole-free using the cast-in channels.

4.2 Quality Control of Pre-embedding Construction

  • Channel sealing inspection: Before pre-embedding construction, the integrity of channel sealing tape, filler, and end caps should be checked to prevent grout from penetrating into the channel during concrete pouring and causing blockage.

  • Positioning accuracy: During channel pre-embedding, positioning should be performed in combination with formwork dimensions to ensure that channel elevation and plan position meet design requirements. The channel surface should be flush with the concrete component surface.

  • Fixing reliability: Channels should be reliably fixed to formwork or rebar cages to prevent displacement during concrete pouring.

V. Technical Advantages of Daring Cast-in Channels in Hospital Projects

5.1 Product Technical Parameters

Technical IndicatorDaring Cast-in Channel Parameters
MaterialQ355 steel or 304/316 stainless steel
Surface treatmentHot-dip galvanized, zinc layer thickness ≥70μm, approximately 50 years of outdoor service life
Thinnest steel sectionNo less than 4mm, with load-bearing performance approximately 30% better than comparable products
Applicable standardsGB/T 38525-2020、JG/T 560-2019
Testing and certificationMultiple tests including 2 million cycles of fatigue resistance, fire resistance, zinc layer thickness, mechanical properties, yield strength, and elongation
Product systemWelded cast-in channels (channel inserts), riveted cast-in channels, weld-free plate channels, and Type A/Type B plate-slot cast-in channels
AccessoriesT-head bolts (compatibility testing is performed for corresponding models to ensure proper fit)

5.2 Construction Advantages of Fire-Free Installation

The installation of cast-in channels requires no welding, flame cutting, grinding and rust removal, or painting, greatly reducing smoke, harmful gases, and noise on site. This not only benefits workers' health but also reduces interference with the surrounding environment and other contractors. For hospital renovation and expansion projects, the cast-in channel solution can prevent other areas from becoming unusable due to construction pollution.

5.3 Full-Process Technical Support

Daring has been deeply engaged in the field of building anchoring for more than 20 years, and its cast-in channel products are widely used in high-end curtain walls, rail transit, utility tunnel industrial applications, and other fields. Daring can provide hospital projects with full-process support services, from BIM layout coordination and channel selection calculations to on-site technical guidance. Daring cast-in channels hold complete CRCC railway product certification and ISO9001 quality management system certification, and the company has been recognized as a High-Tech Enterprise and a specialized, refined, distinctive, and innovative SME; it has served more than 3,000 high-end engineering projects in China.

VI. Frequently Asked Questions

Q1Where are cast-in channels mainly used in hospital buildings?
They are mainly used in two areas: first, mechanical and electrical pipeline support systems, including the suspended installation of air-conditioning water pipes, fire sprinkler pipes, medical gas pipelines, and cable trays; second, medical equipment suspension systems, including the installation and fixing of operating room pendant towers, surgical lights, medical bridges, and ward infusion tracks.
Q2What special requirements apply to supports and hangers for medical gas pipelines in hospitals?
According to GB 51039-2014 and related codes, medical gas pipelines in clean operating departments should have dedicated supports and hangers and should not be installed on the same supports as other pipelines. The distance between medical gas pipelines and gas or corrosive gas pipes should be greater than 1.5m, and the parallel distance from electrical conduits should be greater than 0.5m. Anti-static corrosion and insulation treatment should be applied at the contact points between the pipelines and their supports and hangers.
Q3Why are cast-in channels suitable for hospital renovation and expansion projects?
Hospital renovation and expansion projects are often carried out while some areas remain in normal operation. The cast-in channel solution requires no drilling, no welding, and produces no dust or noise during the mechanical and electrical installation stage, avoiding situations where construction contamination renders other areas unusable. This is especially important for areas with high environmental requirements such as clean operating departments and ICUs.
Q4What is the requirement for the effective embedment depth of cast-in channels?
According to the relevant technical specifications, the effective embedment depth of cast-in channels should be no less than 40mm. When the ratio between the thickness of the concrete member and the effective embedment depth meets specific conditions, the effective embedment depth should be taken according to the dedicated diagram. During the scheme design stage, the channel selection should be confirmed in conjunction with the structural floor slab thickness.
Q5How do cast-in channels work with seismic supports and hangers?
Hospitals are Category B fortified buildings, and mechanical and electrical pipelines in regions with a design seismic intensity of 6 or above must be equipped with seismic supports and hangers. In the cast-in channel solution, the base of the seismic support is fixed to the cast-in channel by T-head bolts, and the diagonal brace is connected to the lateral or longitudinal channel. Compared with post-drilled solutions, the teeth of the T-head bolt engage with the teeth of the cast-in channel, giving better slip resistance, and the installation process involves no hot work.
Q6How does BIM technology support cast-in channel construction?
The specific process is as follows: the mechanical and electrical pipelines are comprehensively laid out using a BIM 3D model to generate a support-and-hanger model and positioning drawings, from which the positioning drawing for the structural cast-in channels is determined. During structural embedding, the finished channels are embedded according to the drawings; during the mechanical and electrical installation stage, the supports and hangers are installed on the cast-in channels without drilling. BIM coordination is the key link in ensuring accurate positioning of cast-in channels.

Daring cast-in channel products comply with GB/T 38525-2020 and JG/T 560-2019 standards and are made of Q355 steel or 304/316 stainless steel with a hot-dip galvanized surface and a zinc coating thickness of 70μm. Daring also supplies T-head bolts to match the corresponding channel models, and compatibility tests are carried out on the T-head bolts to ensure a proper match. Daring can provide hospital projects with full-process support services, from BIM layout coordination and channel selection calculations to on-site technical guidance. For cast-in channel selection and construction scheme design for specific projects, please consult the Daring technical team.

References

GB 51039-2014 Code for Design of General Hospital Buildings — requirements for setting supports and hangers for medical gas systems

GB 50981-2014 Code for Seismic Design of Building Mechanical and Electrical Engineering — mandatory requirements for seismic supports and hangers in Category B fortified buildings

GB 50333-2013 Technical Code for Building of Clean Operating Departments in Hospitals — pipeline installation requirements for clean operating departments

GB/T 38525-2020 Channel-Shaped Embedded Components for Building Curtain Walls — product classification, technical requirements, and inspection rules

JG/T 560-2019 Channel-Shaped Embedded Components for Buildings — technical requirements for cast-in channels

CECS Technical Specification for Prefabricated Hospital Buildings — requirements for embedded components and mechanical connections for piped arrays

Daring website — Differences between cast-in channels and plate-type embedded components in cost and application scenarios, with Daring selection recommendations

Daring website — What is the difference between cast-in channels and plate-slot cast-in channels? A selection comparison guide

Daring website — Product parameters of welded cast-in channels

Daring website — How to choose a cast-in channel manufacturer? Qualifications and project references are key

Daring website — Cast-in channel product series

Back to Daring Home  Back to Top