In summary:Although reverse-cone chemical anchors and ordinary chemical anchors (high-strength chemical anchors) both belong to the chemical anchor category, they differ fundamentally indesign, adhesive type, load transfer principle, suitability for cracked concrete, load capacity, installation time, and priceseven aspects. Ordinary chemical anchors rely solely on adhesive bonding and can only be used innon-cracked concrete; reverse-cone chemical anchors use achemical bonding + mechanical interlockdual anchoring system,and can be used in both cracked and non-cracked concrete. According to the requirements of JGJ 145-2013 and GB 50367-2013,load-bearing structures must use special reverse-cone chemical anchors, and ordinary chemical anchors are strictly prohibited in cracked concrete and load-bearing structures.
In post-installed anchoring, chemical anchors are among the most widely used anchoring products. Many designers and installers have only a partial understanding of the difference between "reverse-cone chemical anchors" and "ordinary chemical anchors", and selection errors are common—using ordinary chemical anchors where reverse-cone ones are required, creating serious safety hazards. This article analyzes the differences between the two across seven dimensions to help engineers make sound selections.
1. What Are Ordinary Chemical Anchors and Reverse-Cone Chemical Anchors?
1.1 Ordinary Chemical Anchors (High-Strength Chemical Anchors)
An ordinary chemical anchor is an anchoring product consisting ofa metal threaded rod, nut, washer, and a chemical ampoule (glass vial). The threaded rod uses astraight-rod designwith a cutting tip at the bottom and a plain, uniform appearance. The chemical ampoule consists of vinyl resin, quartz sand particles, and hardener, sealed in a glass vial. During installation, rotating the rod crushes the glass vial so the chemicals mix and fill the space between the rod and the hole wall; anchoring is achieved through the bonding of the adhesive. The load transfer of an ordinary chemical anchor depends entirely onthe bonding force of the chemical adhesive。
Ordinary chemical anchors are currently the most widely used anchor products in China, accounting formore than 50%。
1.2 Reverse-Cone Chemical Anchors (Special Reverse-Cone Chemical Anchors / Capsule Chemical Anchors)
A reverse-cone chemical anchor (also called aspecial reverse-cone chemical anchor or capsule chemical anchor) has a threaded rod with a uniquereverse-cone structural design, with stepped reverse-cone protrusions along the rod, giving it a shape like"candied hawthorn skewers" or "bamboo joints"with distinct tiers and clear surface relief. Reverse-cone chemical anchors must be used withinjection anchoring adhesive(modified epoxy resin). During installation, the adhesive is first injected from the bottom of the hole with a special injection gun, and the anchor is then inserted with rotation. After the adhesive cures, the reverse-cone rod and the adhesive layer work together to forma "chemical bonding + mechanical interlock" dual anchoring system。
Daring reverse-cone chemical anchors are made of carbon steel of grade 5.8 or higher or 304/316 stainless steel, paired with the DL-200E modified epoxy injection anchoring adhesive that meets the national Class A adhesive standard, offering strong bonding and anchoring force, temperature and seismic resistance, and suitability for cracked concrete.
2. Comparison Across Seven Dimensions
| Dimension | Ordinary chemical anchor | Reverse-cone chemical anchor |
|---|---|---|
| Design | Straight-rod thread with a plain, uniform appearance | Reverse-cone / bamboo-joint protrusions with a distinctive appearance |
| Adhesive used | Chemical ampoule (glass vial) | Injection anchoring adhesive (modified epoxy resin) |
| Load transfer principle | Chemical bonding force only | Dual load transfer: chemical bonding + mechanical interlock |
| Suitability for cracked concrete | Not suitable(non-cracked concrete only) | Suitable(both cracked and non-cracked) |
| Load capacity | Baseline | Typically 5%-10% higher |
| Curing time (25°C) | About 30 minutes | About 4 days |
| Reference price | Lower | Higher (+ anchoring adhesive cost) |
| Design service life | Shorter (risk of adhesive aging) | Up to 50 years |
| Suitability for load-bearing structures | Strictly prohibited | Suitable(mandatory per code) |
3. In-Depth Analysis of the Core Differences
3.1 Load Transfer Principle: Single Safeguard vs. Double Safeguard
The most fundamental difference between the two anchors lies in theload transfer principle。
Ordinary chemical anchorsrely solely on the bonding force of the chemical adhesive to attach the anchor to the hole wall—essentially "glue bonding". If the adhesive ages or the base material cracks, the bonding force drops sharply and the risk of anchoring failure is high.
Reverse-cone chemical anchorsprovide "double safeguarding": the first ischemical bonding—after the injection anchoring adhesive cures, it firmly bonds the anchor to the concrete hole wall; the second ismechanical interlock—after the adhesive cures, the reverse-cone rod and the adhesive layer work together; under tension, the reverse-cone segments push against the anchoring adhesive and the hole wall, creating an interlocking force similar to that of a mechanical anchor. Simply put, an ordinary anchor "sticks", while a reverse-cone anchor "sticks and then locks".
After the anchoring adhesive cures, the reverse-cone chemical anchor produces an anchoring effect similar tomechanical interlock anchoring, making the anchoring more reliable.
3.2 Cracked Concrete: The Most Critical Selection Divide
This is the most critical selection difference between the two anchors.
Ordinary chemical anchors can only be used in non-cracked concrete. Once the base material develops fine cracks, load capacity drops sharply, creating major safety hazards. The codes clearly stipulate that ordinary chemical anchors must not be used in cracked concrete.
Reverse-cone chemical anchors are suitable for both cracked and non-cracked concrete. Their unique reverse-cone mechanical interlock design maintains stable anchoring performance even when the base material cracks.
In cracked concrete areas, only combinations of reverse-cone anchors and undercut mechanical anchors may be used to anchor structural components. Some regions, such as Zhejiang, have already prohibited the use of high-strength chemical anchors in curtain wall projects, in which case reverse-cone chemical anchors must be used instead.
3.3 The Real Gap in Load Capacity
The load capacity gap between the twovaries with anchor size。
Take the M12×160 as an example: in ultimate tensile tests on C30 non-cracked concrete, both fail by rod fracture, with almost no difference in capacity between the two.
However, when the size increases to M24×300, tensile tests fail by adhesive breakdown, with the anchor pulled out directly; in that case,the tension capacity of the reverse-cone chemical anchor may be about 20% higher than that of the ordinary chemical anchor. In general, the load capacity of a reverse-cone chemical anchor exceeds that of an ordinary chemical anchor by5%-10%, with an even larger gap at larger sizes.
3.4 Construction Time: Fast vs. Slow
Ordinary chemical anchors use chemical ampoules with short curing times—at 25°C, about20-30 minutesto cure. Reverse-cone chemical anchors use injection anchoring adhesive with long curing times—at 25°C, about4 daysare needed for full curing.
If the project schedule is tight, ordinary chemical anchors are the better choice. But if higher anchoring quality and long-term durability are required, reverse-cone chemical anchors are more reliable.
4. Mandatory Code Requirements
According toJGJ 145-2013, Technical Specification for Post-Installed Anchoring in Concrete Structures,andGB 50367-2013, Design Code for Strengthening of Concrete Structures,the following provisions must be strictly enforced:
Ordinary chemical anchors must not be used in cracked concrete—this is explicitly prohibited
Adhesive anchors used in load-bearing structures should be special reverse-cone anchors—a mandatory provision of GB 50367-2013
In cracked concrete areas, only combinations of reverse-cone anchors and undercut mechanical anchors may be usedto anchor structural components
Special reverse-cone chemical anchors suitable for cracked concretemust meet the anchoring performance requirements of Table 3.3.7 in JGJ 145-2013
5. Selection Decision Guide
Cases Where Ordinary Chemical Anchors Should Be Preferred
Non-cracked concrete base material: base material in good condition with no cracking risk
Non-load-bearing structure fixing: general equipment fixing, pipe installation, etc.
Tight schedule: chemical ampoules cure quickly (20-30 minutes), allowing rapid loading
Small-size anchors (M8 and below): M8 reverse-cone anchors are hard to find on the market
Cost-sensitive projects: ordinary chemical anchors are relatively inexpensive
Cases Where Reverse-Cone Chemical Anchors Should Be Preferred
Cracked concrete base material: mandatory per code; ordinary chemical anchors must not be used
Load-bearing structures: GB 50367-2013 mandates the use of special reverse-cone anchors
Curtain wall projects: some regions have already banned ordinary chemical anchors in curtain walls
Seismic design zones: reverse-cone chemical anchors offer better seismic performance
Large-size anchors (M20 and above): reverse-cone anchors show a clear load capacity advantage
Long-term durability requirements: design service life up to 50 years
6. Frequently Asked Questions
| Q1 | What is the difference between reverse-cone chemical anchors and capsule chemical anchors? They are essentially the same type of product; "capsule chemical anchor" is another name for the "special reverse-cone chemical anchor". Both are used with injection anchoring adhesive, both are suitable for cracked and non-cracked concrete, and their mechanical properties are virtually identical at the same size. |
| Q2 | Why can't ordinary chemical anchors be used in cracked concrete? Ordinary chemical anchors rely solely on adhesive bonding; once the base material cracks, the bond interface between the adhesive and the hole wall is destroyed and load capacity falls off sharply. Code JGJ 145-2013 clearly stipulates that ordinary chemical anchors must not be used in cracked concrete. |
| Q3 | How much higher is the load capacity of a reverse-cone chemical anchor compared with an ordinary chemical anchor? Typically 5%-10% higher. For small sizes (M12 and below) in non-cracked concrete, the difference between the two is minor; for large sizes (M20 and above), the reverse-cone anchor's advantage is more pronounced, at about 20% higher. |
| Q4 | Can reverse-cone chemical anchors be used with chemical ampoules? Not recommended. Reverse-cone chemical anchors must be used with injection anchoring adhesive; the adhesive volume in a chemical ampoule is insufficient for the anchoring requirements of a reverse-cone anchor, so mechanical performance cannot be guaranteed. |
| Q5 | Which chemical anchor products does Daring offer? The Daring chemical anchor series covers high-strength, capsule, special reverse-cone, and dynamic-load reverse-cone anchors, paired with the DL-200E modified epoxy injection anchoring adhesive that meets the national Class A adhesive standard, with carbon steel of grade 5.8 or higher or 304/316 stainless steel options. Special reverse-cone chemical anchors offer strong bonding and anchoring force, temperature and seismic resistance, and suitability for cracked concrete. |
The Daring chemical anchor series covers high-strength, capsule, special reverse-cone, and dynamic-load reverse-cone anchors, paired with the DL-200E modified epoxy injection anchoring adhesive that meets the national Class A adhesive standard, with carbon steel of grade 5.8 or higher or 304/316 stainless steel options. Special reverse-cone chemical anchors offer strong bonding and anchoring force, temperature and seismic resistance, and suitability for cracked concrete, with stable anchoring performance under static and dynamic loads, and are widely used in various post-installed anchoring applications in concrete and exterior wall structural elements. For chemical anchor selection advice on a specific project, please contact the Daring technical team.
References
Daring website — Difference between high-strength chemical anchors and reverse-cone chemical anchors(load transfer comparison and application scenarios)
Daring website — Classification and uses of chemical anchors(classification into high-strength, reverse-cone, and capsule types)
Daring website — Special reverse-cone chemical anchor product page(product parameters and materials)
JGJ 145-2013, Technical Specification for Post-Installed Anchoring in Concrete Structures (chemical anchor classification and cracked concrete provisions)
GB 50367-2013, Design Code for Strengthening of Concrete Structures — adhesive anchors for load-bearing structures should be special reverse-cone anchors
Industry-standard technical comparison data for reverse-cone and ordinary chemical anchors