To start with the conclusion:According to JGJ 145-2013 Technical Specification for Post-Installed Fastenings in Concrete Structures, theminimum spacing of chemical anchors is 6 times the rod diameter (6d),and the minimum edge distance is also 6 times the rod diameter (6d). Taking an M12 chemical anchor as an example, both the minimum spacing and the minimum edge distance are72mm; for M16, both are96mm. When anchor spacing or edge distance falls below the standard requirements, load capacity drops substantially and anchoring may even fail.During installation, anchors must be laid out strictly according to the standards, and the load capacity of anchor groups must account for reduction factors for spacing and edge distance.
In building post-installed anchoring projects, the installation spacing of chemical anchors is one of the key factors determining the load capacity of the anchoring system. Many installers have only a partial understanding of chemical anchor spacing requirements, resulting in arbitrary field layouts and inconsistent anchoring quality. Too small a spacing weakens anchoring load capacity, while too large a spacing wastes base material space. Based on JGJ 145-2013 Technical Specification for Post-Installed Fastenings in Concrete Structures, this article systematically explains key parameters such as the spacing, edge distance, and anchorage depth of chemical anchors.
I. Core Spacing Requirements for Chemical Anchors
1.1 Minimum spacing: 6 times the rod diameter
According to Table 7.1.2 of JGJ 145-2013 Technical Specification for Post-Installed Fastenings in Concrete Structures,the minimum spacing of chemical anchors is 6 times the anchor outer diameter (6d)。
| Anchor specification | Minimum spacing (6d) | Minimum edge distance (6d) |
|---|---|---|
| M8 | 48mm | 48mm |
| M10 | 60mm | 60mm |
| M12 | 72mm | 72mm |
| M16 | 96mm | 96mm |
| M20 | 120mm | 120mm |
| M24 | 144mm | 144mm |
Note: d is the anchor outer diameter. The values above are the minimums specified by the standard; in actual projects they should be determined according to the anchor product's certification report and the specific working conditions.
1.2 Minimum edge distance: also 6 times the rod diameter
Theminimum edge distance of chemical anchors is likewise 6 times the anchor outer diameter (6d). The edge distance refers to the minimum distance from the anchor center to the edge of the concrete base material. When anchors are placed close to member edges, insufficient edge distance reduces the concrete cone failure area and significantly lowers load capacity.
In addition, the minimum edge distance of anchorsshould also not be less than twice the maximum aggregate size. If the maximum aggregate size in the concrete is 30mm, the edge distance should be at least 60mm and no less than the calculated 6d value.
II. Anchorage Depth and Base Material Thickness Requirements
2.1 Minimum base material thickness
According to Clause 7.1.1 of JGJ 145-2013, the thickness of the concrete base material for chemical anchorsshould not be less than hef + 2d₀ and should exceed 100mm, where hef is the effective embedment depth of the anchor and d₀ is the drilling diameter.
Taking an M12 chemical anchor as an example: with a drilling diameter d₀ of 14mm and an effective embedment depth hef of 110mm, the minimum base material thickness is 110 + 2 × 14 = 138mm, and it must exceed 100mm.
2.2 Minimum anchorage depth
The minimum anchorage depth of chemical anchors should comply with the requirements of Table 7.1.7 of JGJ 145-2013:
| Chemical anchor diameter d (mm) | Minimum anchorage depth (mm) |
|---|---|
| ≤10 | 60 |
| 12 | 70 |
| 16 | 80 |
| 20 | 90 |
| ≥24 | 4d |
Note: data are taken from Table 7.1.7 of JGJ 145-2013. The effective anchorage depth of chemical anchors should not exceed 20d.
III. Consequences of Insufficient Spacing
When the spacing or edge distance of chemical anchors is less than the standard requirements, the anchoring system is adversely affected as follows:
Substantial reduction in load capacity: when spacing is too small, the concrete cone failure surfaces of adjacent anchors overlap, and the group anchor effect prevents simple superposition of load capacity. When anchor spacing is less than 3d, load capacity reaches its minimum and the concrete failure cones of adjacent anchors in the base material essentially coincide.
Insufficient edge distance causes brittle failure: with too small an edge distance, the concrete edge is prone to cone failure when the anchor is under tension, significantly reducing load capacity.
Concrete splitting during installation: with too small a spacing or edge distance, anchor installation may cause concrete splitting failure.
Research shows that when both the spacing and edge distance of an anchor system are no less than 8d, load capacity reaches its maximum, about 40% higher than at the 6d minimum required by the specification.
IV. Spacing Comparison of Different Anchor Types
According to Table 7.1.2 of JGJ 145-2013, different anchor types have different minimum spacing and minimum edge distance requirements:
| Anchor type | Minimum spacing s | Minimum edge distance c |
|---|---|---|
| Displacement-controlled expansion anchors | 6d | 10d |
| Torque-controlled expansion anchors | 6d | 8d |
| Undercut anchors | 6d | 6d |
| Chemical anchors | 6d | 6d |
As shown in the table, the edge distance requirement for chemical anchors (6d) is far smaller than that for expansion anchors (8d-10d), because chemical anchors generate no expansion stress and pose a lower risk of squeeze failure of the base material.
V. Installation Key Points and Precautions
5.1 Drilling and positioning
Before drilling, layout and positioning should be carried out accurately according to the design drawings to ensure anchor spacing and edge distance meet the standard requirements. The deviation of the center-to-center spacing between two adjacent groups of chemical anchors should preferably not exceed ±10mm.
5.2 Avoiding unfavorable locations
Anchors should not be placed within the concrete cover, and the effective anchorage depth should not include decorative or plaster layers. Anchor fixing positions should avoid unfavorable areas such as expansion joints and segment gaps.
5.3 Remedial measures for insufficient spacing
When anchor spacing cannot meet the standard requirements, the following measures can be taken:
Increase the anchorage depth: appropriately increasing the anchorage depth can partially offset the load capacity reduction caused by excessively small spacing.
Load capacity reduction calculation: calculate the load capacity reduction for anchor groups in accordance with Chapter 6 of JGJ 145-2013.
Adjust the layout: where conditions permit, re-plan the anchor layout to increase spacing and edge distance.
VI. FAQs
| Q1 | What is the minimum spacing for chemical anchors? According to JGJ 145-2013, the minimum spacing of chemical anchors is 6 times the rod diameter (6d). For example, the minimum spacing is 72mm for M12 anchors and 96mm for M16. |
| Q2 | What is the minimum edge distance for chemical anchors? The minimum edge distance of chemical anchors is likewise 6 times the rod diameter (6d). In addition, the edge distance should not be less than twice the maximum aggregate size. |
| Q3 | What are the consequences of insufficient spacing? Insufficient spacing causes the concrete cone failure surfaces of adjacent anchors to overlap, so group anchor load capacity cannot be simply superposed and overall load capacity drops substantially. Load capacity is lowest when spacing is less than 3d. |
| Q4 | What are the anchorage depth requirements for chemical anchors? According to Table 7.1.7 of JGJ 145-2013, the minimum anchorage depth is 70mm for M12, 80mm for M16, 90mm for M20, and 4d for M24 and above. |
| Q5 | How do the spacing requirements of chemical anchors and expansion anchors differ? The minimum edge distance is 6d for chemical anchors, 8d for torque-controlled expansion anchors, and 10d for displacement-controlled expansion anchors. Chemical anchors generate no expansion stress, so their edge distance requirements are smaller. |
| Q6 | How are the spacing and edge distance of anchor groups determined? The minimum spacing and minimum edge distance of anchors in an anchor group should be determined according to the anchor product's certification report; if no certification report is available, they should comply with Table 7.1.2 of JGJ 145-2013. |
The Daring chemical anchor series covers high-strength, capsule, and special reverse-cone anchors, paired with Daring's DL-200E modified epoxy injection anchoring adhesive meeting the national Grade A adhesive standard, available in carbon steel of Grade 5.8 or above, or in 304/316 stainless steel. Products are manufactured and tested strictly in accordance with JGJ 145-2013, ensuring safe and reliable anchoring. For chemical anchor spacing calculations and selection advice on a specific project, please contact the Daring technical team.
References
Daring website — Installation Spacing of Chemical Anchors(interpretation of the spacing and edge distance provisions in JGJ 145-2013)
JGJ 145-2013 Technical Specification for Post-Installed Fastenings in Concrete Structures — Table 7.1.2, minimum anchor spacing and minimum edge distance
JGJ 145-2013 Technical Specification for Post-Installed Fastenings in Concrete Structures — Table 7.1.7, minimum anchorage depth of chemical anchors
JGJ 145-2013 Technical Specification for Post-Installed Fastenings in Concrete Structures — Clause 7.1.1, base material thickness requirements
Experimental Study on the Mechanical Behavior of Chemical Anchor Groups — Influence of Spacing and Edge Distance on Load Capacity
