Product Knowledge

Installation spacing for chemical anchors

Views: 0Posted on: 2019-01-15

Aboutthe installation method of chemical anchors, many people are familiar with it, but more people may have only a partial understanding of the installation spacing requirements of chemical anchors. The spacing requirements mentioned here are rather general; the author believes they should include the relationship between embedment depth and concrete thickness, the installation edge distance, and the installation spacing. This article will give the standard answers strictly according to the provisions of the codes.

Relationship between embedment depth and concrete thickness

JGJ 145-2013 Technical Specification for Post-Installed Anchoring in Concrete Structures contains the following provisions:
7.1.1 The thickness h of the concrete substrate shall meet the following requirements:

1 For expansion anchors and undercut anchors, h shall not be less than 2 hef, and h shall be greater than 100mm. hef is the effective embedment depth of the anchor.

2 For chemical anchors, h shall not be less than hef+2d0, and h shall be greater than 100mm. d0 is the drill hole diameter.

The same code also contains the following provisions:

7.1.7 The minimum embedment depth of chemical anchors shall meet the requirements of Table 7.1.7.

Table 7.1.7 Minimum embedment depth of chemical anchors

Chemical anchor diameter d (mm)

Minimum embedment depth (mm)

≤10

60

12

70

16

80

20

90

≥24

4d

A brief summary yields the following conclusions:

① The concrete thickness must not be less than 100mm, and for chemical anchors, the thickness should be no less than hef+2d0;

② The minimum embedment depth of chemical anchors shall meet the table above; failure to meet it can be judged as non-compliant.

Installation edge distance and spacing

The same code also states the following about installation edge distance and spacing:

7.1.2 The minimum spacing s and minimum edge distance c of anchor groups shall be determined according to the anchor product's certification report; when there is no certification report, they shall comply with Table 7.1.2. The minimum edge distance c of anchors shall in no case be less than twice the maximum aggregate size.

Table 7.1.2 Minimum spacing s and minimum edge distance c of anchors

Anchor type

Minimum spacing s

Minimum edge distance c

Displacement-controlled expansion anchor

6dnom

10dnom

Torque-controlled expansion anchor

6dnom

8dnom

Undercut anchor

6dnom

6dnom

Chemical anchor

6dnom

6dnom

Note: dnom is the outer diameter of the anchor.

The table clearly shows that the minimum edge distance of chemical anchors is 6 times the rod diameter, and the minimum spacing is also 6 times the rod diameter. When the edge distance is small, the anchor's load performance will be considerably reduced.




Back to Daring Home  Back to Top