Curtain wall construction has always been governed by relevant codes; you cannot simply use whatever anchor you like. The reference standards below are provided to ensure construction outcomes meet national and regional standards.
Provisions of national standards
Many practitioners are very familiar with JGJ 145-2013 Technical Specification for Post-Installed Anchoring in Concrete Structures. As the reference standard for anchors, it strictly specifies the conditions for anchor selection:
4.1.1 Anchors shall be selected according to anchor performance, base material shape, the load characteristics of the anchorage connection, the type of structure being connected, and seismic precautions. The scope of application of anchors for connections of structural components shall comply with Table 4.1.1-1, and for connections of non-structural components shall comply with Table 4.1.1-2.
Table 4.1.1-1 Scope of application of anchors for connections of structural components
Anchor load state and precautionary intensity Anchor type | Tension, edge shear, and combined tension-shear | Compression, central shear, and combined compression-shear | |||
Non-seismic | 6, intensity 7 | 8 degrees | ≤ intensity 8 | ||
0.2g | 0.3g | ||||
Mechanical anchors | Expansion anchors | Torque-controlled anchors | Applicable | Not applicable | Applicable |
Displacement-controlled anchors | Not applicable | ||||
Undercut anchors | Applicable | Not applicable | Applicable | ||
Chemical anchors | Special reverse-cone chemical anchors | Applicable | Not applicable | Applicable | |
Ordinary chemical anchors | Not applicable | Applicable |
Table 4.1.1-2 Scope of application of anchors for connections of non-structural components
Anchor load state Anchor type | Tension, edge shear, and combined tension-shear (seismic precautionary intensity ≤ 8) | Compression, central shear, and combined compression-shear (seismic precautionary intensity ≤ 8) | |||||
Lifeline projects | Non-lifeline projects | Lifeline projects | Non-lifeline projects | ||||
Mechanical anchors | Expansion anchors | Torque-controlled anchors | Suitable for cracked concrete | Applicable | |||
Suitable for uncracked concrete | Not applicable | Applicable | |||||
Displacement-controlled anchors | Not applicable | Applicable | |||||
Undercut anchors | Applicable | ||||||
Chemical anchors | Special reverse-cone chemical anchors | Applicable | |||||
Ordinary chemical anchors | Suitable for cracked concrete | Applicable | |||||
Suitable for uncracked concrete | Not applicable | Applicable | |||||
2 2. Anchors suitable for cracked concrete refer to anchors that meet the anchoring performance requirements for cracked concrete and for repeated opening and closing of cracks.
If you read the table carefully, undercut anchors and special reverse-cone chemical anchors have a broader scope of application, while expansion anchors and ordinary chemical anchors are subject to many restrictions.Absent local codes, all the anchors involved may be used under specific service conditions.
Restrictions of local codes
But some regions are stricter about curtain wall construction, such as Zhejiang and Shanghai, which impose additional requirements on anchor selection.
ZJSP16-2013-002, Safety Technical Requirements for Building Curtain Walls, Zhejiang Construction Document (2013) No. 2, contains the following statement:
4.6 Post-installed inserts for building curtain walls shall, per design requirements, use reliable anchors such as undercut mechanical anchors and capsule chemical anchors; ordinary chemical anchors shall not be used. When capsule chemical anchors are used, the supplier shall provide a high-temperature resistance test report for the chemical anchors.
This puts it even more plainly: expansion anchors and ordinary chemical anchors must not be used on building curtain walls in Zhejiang, and capsule chemical anchors must pass high-temperature testing when used.
The above are Zhejiang's requirements for anchor selection, but neighboring Shanghai differs. DGJ08-56-2012, Technical Specification for Building Curtain Wall Engineering in Shanghai, contains the following statement:
9.5.8 When the curtain wall structure is connected to the main structure using post-installed inserts, anchor inserts shall be arranged reasonably according to load conditions to ensure a reliable connection, and shall comply with the following provisions:
1 Anchors for post-installed inserts may be self-undercutting anchors, mold-undercutting anchors, special reverse-cone anchors, or chemical anchors. The tensile performance of the anchor steel must be re-tested, and the results shall comply with GB 50367 Design Code for Strengthening of Concrete Structures.
5 Post-installed inserts requiring welding after positioning shall use mechanical undercut anchors, or chemical anchors and mechanical anchors arranged alternately. For post-installed inserts in which chemical anchors account for more than half, no welding shall be performed on their components or connectors after positioning.
In other words, expansion anchors must not be used on building curtain walls in Shanghai, and when welding is required, chemical anchors must not exceed half of the anchors used.In actual use, however, base plates fixed with anchors are often welded, so when working in Shanghai, particular attention must be paid to the proportion of chemical anchors.