First, the conclusion:Ordinary chemical anchorscannotfor use in cracked concrete. According toJGJ 145-2013, Technical Specification for Post-Installed Anchorage of Concrete StructuresandGB 50367-2013, Code for Design of Strengthening Concrete Structures, ordinary chemical anchorsmust not be used in cracked concreteand load-bearing structures. In cracked concrete,Special reverse-cone chemical anchors(capsule chemical anchors) orUndercut mechanical anchors. Special reverse-cone anchors achievereverse-cone mechanical interlock + chemical bondingwith a dual load-bearing mechanism, they maintain stable anchoring force even when the substrate cracks. Daring capsule chemical anchors are paired with DL-200E modified epoxy injection anchoring adhesive, which meets the national Class A adhesive standard, offering strong bond anchoring, temperature and seismic resistance, and suitability for cracked concrete. They have passed S-class anchor certification, 2 million fatigue cycles, 120-minute fire resistance and numerous other tests.
In post-installed anchoring work, concrete cracking isthe most common substrate defectone of. Many designers and construction personnel have a misconception about whether "chemical anchors can be used in cracked concrete" — some believe that increasing the embedment depth is sufficient, while others think injecting adhesive to fill the cracks solves the problem. Based on code requirements, load-bearing mechanisms and product selection, this article systematically addresses the use of chemical anchors in cracked concrete.
I. Explicitly prohibited by the standards: ordinary chemical anchors must not be used in cracked concrete
1.1 Core code provisions
According toJGJ 145-2013, Technical Specification for Post-Installed Anchorage of Concrete Structures, ordinary chemical anchorsmust not be used in cracked concrete. Clause 3.3.7 of this code explicitly specifies the anchor types applicable to cracked concrete, and ordinary chemical anchors are not among them.
According toGB 50367-2013, Code for Design of Strengthening Concrete Structures, adhesive anchors used in load-bearing structures should bespecial reverse-cone adhesive anchors, while ordinary chemical anchorsare strictly prohibited in load-bearing structures and cracked concrete。
At the same time,JGJ 336-2016, Technical Code for Engineering of Artificial Panel Curtain Wallsclause 5.5.4 also explicitly stipulates that post-installed anchors used incracked concretesubstrates should becapsule chemical anchors suitable for cracked concrete, and should meet the relevant requirements of JGJ 145-2013. Ordinary chemical anchorsmust not be used in cracked concrete substrates。
1.2 Why the standards prohibit this
Ordinary chemical anchors rely solely onchemical bond strengthto fix the threaded rod to the borehole wall. When the concrete cracks:
the crack willrun through the anchorage zone, destroying the bonded interface between the resin and the borehole wall
bond strengthdrops precipitously, and load capacity cannot be guaranteed
under load, the anchor maybe pulled out directly, without any warning
The anchoring resin layer of an ordinary chemical anchor is generally ≤3 mm thick, and when a crack opens the resin layer is easily torn. For this reason, the standards explicitly prohibit the use of ordinary chemical anchors in cracked concrete on safety grounds.
II. Anchor types that can be used in cracked concrete
2.1 Special reverse-cone chemical anchors (capsule chemical anchors)
The threaded rod of a special reverse-cone chemical anchor (also called a capsule chemical anchor) uses a uniquereverse-cone structural design, with stepped reverse-cone protrusions along the rod, resembling"candied haws on a stick" or "bamboo joints". Its load-bearing mechanism isdual load bearing by chemical bonding + mechanical interlock:
First: chemical bonding— after the injection anchoring adhesive cures, it firmly bonds the anchor to the concrete borehole wall
Second: mechanical interlock— after the resin cures, the reverse-cone threaded rod acts together with the resin layer; under tension the reverse cone exerts a compressive keying action on the adhesive and borehole wall, creating a keying force similar to that of a mechanical anchor
In short, an ordinary anchor "sticks," while a reverse-cone anchor "sticks" and then "locks" in place.Even if the substrate cracks, the mechanical interlock still maintains anchoring force. Daring capsule chemical anchors have passedS-class anchor certification— according to JG/T 160-2017, S-class anchors are suitable for cracked concrete and seismic zones and represent the highest classification of mechanical anchors.
2.2 Undercut mechanical anchors
Undercut anchors usereaming at the bottom of the hole to form a mechanical interlock, do not rely on any chemical adhesive,and carry load purely by mechanical interlock. Even in cracked concrete, the keying structure maintains stable anchoring force. Undercut anchors are the type ofload-bearing mechanical anchor mandated by GB 50367-2013, and are equally suitable for cracked concrete.
2.3 Comparison of anchor selection for cracked concrete
| Comparison dimension | Ordinary chemical anchors | Reverse-cone chemical anchors | Undercut anchors |
|---|---|---|---|
| Suitable for cracked concrete | ❌ Strictly prohibited | ✅ Suitable | ✅ Suitable |
| Load-bearing principle | chemical bonding only | bonding + mechanical interlock | pure mechanical interlock |
| Suitable for load-bearing structures | ❌ Strictly prohibited | ✅ Suitable | ✅ Suitable |
| Matching adhesive | Chemical cartridge | Injection anchoring adhesive | no adhesive required |
| carries load after installation | requires a curing wait | requires a curing wait | ready for immediate use |
III. Why special reverse-cone chemical anchors can be used in cracked concrete
3.1 Dual load-bearing mechanism
The core technology of special reverse-cone chemical anchors lies inthe reverse-cone structure. Once the anchor is installed in the hole and the resin has cured, the reverse-cone threaded rod and the resin layer forma mechanical interlock. Under tension, the reverse cone exerts acompressive keying actionon the anchoring adhesive and borehole wall, creating a keying force similar to that of a mechanical anchor. Even if cracking of the substrate destroys the bonded interface between the resin and the borehole wall, themechanical interlock between the reverse cone and the resin layer remains effective, and the anchoring force is maintained.
3.2 S-class anchor certification
According to JG/T 160-2017, Mechanical Anchors for Concrete, anchors are classified by suitability into Class A and Class S:
Class A anchors: suitable only for uncracked concrete
Class S anchors: suitable for cracked concrete and seismic zones, representing the highest classification of mechanical anchors
Daring capsule chemical anchors have passedS-class anchor certification, demonstrating their suitability for cracked concrete and seismic fortification zones.
3.3 The complementary role of injection anchoring adhesive
Daring capsule chemical anchors are paired withDL-200E modified epoxy injection anchoring adhesive, an adhesive meeting the national Class A adhesive standard,with stable chemical properties, temperature resistance and seismic resistance. Compared with chemical cartridges, injection anchoring adhesive offers the following advantages:
flexible control of adhesive volume, ensuring complete filling
the modified epoxy resin'sstability and durability are superior to those of chemical cartridges
suitable forcracked concreteanchor installation in
IV. Precautions for chemical anchor installation in cracked concrete
4.1 Effect of crack width on anchoring
In cracked concrete, crack width is a key factor affecting anchoring performance. According to JGJ 145-2013, anchors used in cracked concrete must satisfy a crack width of ≤0.3mm(serviceability limit state) and ≤0.4mm(seismic fortification state). Before installation,inspect the crack width of the substrate, and if the crack width exceeds the allowable value, repair the crack first or adjust the anchoring scheme.
4.2 Relationship between crack location and anchor hole position
During installation,avoid through-going primary cracks, and the distance between the anchor hole and the crack must satisfy:
the distance between the anchor center and the crackmust not be less than 3 times the anchor diameter
If a crack runs through the embedment depth, you shouldadjust the hole positionor selecta larger-size anchorto increase the safety margin
4.3 Select the correct anchoring adhesive
In cracked concrete,chemical cartridges must never be used(glass tubes); instead,injection anchoring adhesive. The reasons are as follows:
Chemical cartridges rely on the rotating threaded rod to break the glass tube and mix the adhesive; in cracked concretethe resin can hardly fill the cracked area completely
Injection anchoring adhesive can, via an injection gun,actively inject adhesive, ensuring that the resin fills the hole and microcracks
V. Selection decision guide
5.1 Anchor selection decision table for cracked concrete
| Service condition | Applicable anchors | Strictly prohibited |
|---|---|---|
| Non-load-bearing + uncracked concrete | Ordinary chemical anchors, expansion anchors | — |
| Non-load-bearing + cracked concrete | Capsule chemical anchorsand undercut anchors | Ordinary chemical anchors, expansion anchors |
| Load-bearing + uncracked concrete | Undercut anchors, capsule chemical anchors | Ordinary chemical anchors, expansion anchors |
| Load-bearing + cracked concrete | Must usecapsule chemical anchors or undercut anchors | Ordinary chemical anchors, expansion anchors |
| Seismic fortification zone + load-bearing | Must usecapsule chemical anchors or undercut anchors | Expansion anchors, ordinary chemical anchors |
5.2 Core selection principles
Cracked concrete: ordinary chemical anchorsmust not be used, and capsule chemical anchors or undercut anchors must be selected
Load-bearing structures: capsule chemical anchors or undercut anchors must be selected
Seismic fortification zones: S-class anchors must be selected (capsule chemical anchors or undercut anchors)
Tight schedules: undercut anchors are ready for immediate use with no curing wait
VI. Daring anchoring solutions for cracked concrete
6.1 Daring capsule chemical anchors
Daring capsule chemical anchors (special reverse-cone chemical anchors) usea reverse-cone structural design, paired withDL-200E modified epoxy injection anchoring adhesive(national Class A adhesive standard), achievingchemical bonding + mechanical interlockdual load-bearing mechanism, suitable for both cracked and uncracked concrete. The products have passed:
S-class anchor certification: the highest grade for cracked concrete and seismic zones
2 million fatigue cycles: stable anchoring force under cyclic loads
120-minute fire resistance: load capacity maintained even in high-temperature environments
Seismic testing: passed seismic testing by the National Building Materials Testing Center
6.2 Daring undercut anchors
Daring undercut anchors carry load throughpure mechanical interlock, rely on no chemical adhesive, and are suitable for both cracked and uncracked concrete,locking immediately upon installation with no curing required. The series covers M8-M20 sizes, with materials including grade 5.8/8.8 carbon steel and 304/316 stainless steel, and is supplied with original-manufacturer undercutting drill bits and electric installation tools.
VII. Frequently asked questions
| Q1 | Can ordinary chemical anchors be used in cracked concrete? No. According to JGJ 145-2013 and GB 50367-2013, ordinary chemical anchors must not be used in cracked concrete or load-bearing structures. In cracked concrete, special reverse-cone chemical anchors or undercut mechanical anchors must be used. |
| Q2 | Which anchors should be used in cracked concrete? In cracked concrete, special reverse-cone chemical anchors (capsule chemical anchors) or undercut mechanical anchors should be used. Both carry load through mechanical interlock and maintain stable anchoring force even when the substrate cracks. |
| Q3 | What is the difference between ordinary chemical anchors and reverse-cone chemical anchors? Ordinary chemical anchors rely solely on resin bond strength, while reverse-cone chemical anchors use dual load bearing of chemical bonding + mechanical interlock: the reverse cone forms a mechanical interlock with the resin layer, maintaining anchoring force even when the substrate cracks. Reverse-cone chemical anchors have passed S-class anchor certification and are suitable for cracked concrete. |
| Q4 | Are Daring capsule chemical anchors suitable for cracked concrete? Yes. Daring capsule chemical anchors (special reverse-cone chemical anchors), paired with DL-200E modified epoxy injection anchoring adhesive, have passed S-class anchor certification, 2 million fatigue cycles, 120-minute fire resistance, seismic testing and numerous other tests, and are suitable for both cracked and uncracked concrete. |
| Q5 | What should be noted during installation in cracked concrete? Before installation, check the crack width (≤0.3 mm) and ensure the distance from the anchor center to the crack is ≥3d. Injection anchoring adhesive must be used rather than chemical cartridges, so that the resin fills the hole and microcracks. Give priority to products with S-class anchor certification. |
The Daring chemical anchor series covers high-strength, capsule, special reverse-cone and dynamic-load reverse-cone anchors, paired with Daring's DL-200E modified epoxy injection anchoring adhesive, which meets the national Class A adhesive standard. Daring capsule chemical anchors use a reverse-cone structural design and achievechemical bonding + mechanical interlockdual load bearing, and have passed S-class anchor certification, 2 million fatigue cycles, 120-minute fire resistance, seismic testing and numerous other tests, making them suitable for both cracked and uncracked concrete. For advice on selecting an anchoring solution for cracked concrete in a specific project, please consult the Daring technical team.
References
JGJ 145-2013, Technical Specification for Post-Installed Anchorage of Concrete Structures
GB 50367-2013, Code for Design of Strengthening Concrete Structures
JGJ 336-2016, Technical Code for Engineering of Artificial Panel Curtain Walls
JG/T 160-2017, Mechanical Anchors for Concrete