To start with the conclusion: The pull-out force design value of a chemical anchor is not a fixed number; it is determined by anchor size, material strength class, base concrete strength class, embedment depth, and construction quality jointly. Per GB/T 3098.1-2010 Mechanical Properties of Fasteners — Bolts, Screws and Studs, taking an M12×160 property class 5.8 chemical anchor on C30 concrete as an example, its minimum tensile load is 43.8kN, with failure tension reaching over 60kN. Per JGJ 145-2013 Technical Specification for Post-Installed Anchoring in Concrete Structures, the measured load capacity in the on-site pull-out test should be no less than 1.5 times the design value, with no significant displacement growth during 2 minutes of load holding. The load capacity of Daring chemical anchors at standard embedment depth often exceeds the design value by 3-5 times, with ample safety margin.
In post-installed anchoring applications, the design values and testing standards for the pull-out force of chemical anchors are a common focus of designers, construction personnel, and supervisors. Many engineering professionals lack a systematic understanding of questions such as "What is the design value?", "How is on-site testing performed?", and "What are the acceptance criteria?". This article provides a systematic analysis covering design value references, calculation basis, testing standards, and construction impact.
1. Chemical anchor pull-out force design value reference (per GB/T 3098.1-2010)
1.1 Minimum tensile loads of chemical anchors in common sizes
The following are the minimum tensile loads of Daring high-strength chemical anchors at common property classes (5.8 and 8.8), based on Table 4 of GB/T 3098.1-2010 (coarse pitch threads):
| Thread size (d) | Nominal stress cross-sectional area of thread (mm²) | Minimum tensile load, class 5.8 (kN) | Minimum tensile load, class 8.8 (kN) |
|---|---|---|---|
| M8 | 36.6 | 19.0 | 29.2 |
| M10 | 58.0 | 30.2 | 46.4 |
| M12 | 84.3 | 43.8 | 67.4 |
| M14 | 115.0 | 59.8 | 92.0 |
| M16 | 157.0 | 81.6 | 125.0 |
| M20 | 245.0 | 127.0 | 203.0 |
| M24 | 353.0 | 184.0 | 293.0 |
| M30 | 561.0 | 292.0 | 466.0 |
Note: Data are based on Table 4 of GB/T 3098.1-2010 (coarse pitch threads). The minimum tensile strength is 520MPa for class 5.8 and 800MPa for class 8.8. Minimum tensile load = nominal stress cross-sectional area × minimum tensile strength. The values in the table above are standard specified values; actual products should follow their test reports. Common chemical anchor sizes are M8-M30; sizes below M8 and above M30 are rarely used in curtain wall and post-installed anchoring applications.
1.2 Property classes and corresponding mechanical properties
| Property class | Nominal tensile strength (MPa) | Minimum tensile strength (MPa) | Proof stress at 0.2% non-proportional elongation (MPa) | Hardness range (HV) |
|---|---|---|---|---|
| 5.8 | 500 | 520 | — | 160-220 |
| 8.8 | 800 | 800 | 640 | 250-320 |
Note: The hardness range is Vickers hardness (HV), per Table 3 of GB/T 3098.1-2010. Class 5.8 is in the cold-worked condition and class 8.8 in the quenched and tempered condition. The common material classes for chemical anchors are 5.8 and 8.8, corresponding to ordinary carbon steel and high-strength carbon steel respectively.
1.3 Pull-out force limits at different concrete strength classes
Per JGJ 145-2013 Technical Specification for Post-Installed Anchoring in Concrete Structures, the pull-out force limits for chemical anchors at different concrete strength classes are as follows:
| Size | Embedment depth (mm) | Pull-out force limit, C25 (kN) | Pull-out force limit, C30 (kN) |
|---|---|---|---|
| M10 | 90 | 25 | 27 |
| M12 | 110 | 36 | 40 |
| M16 | 130 | 47 | 52 |
| M20 | 160 | 65 | 72 |
| M24 | 220 | 108 | 119 |
These parameters apply to chemical anchors and mechanical anchors in cracked concrete per JGJ 145-2013. Note that when a chemical anchor is subject to a long-term tensile load, the values in the table should be multiplied by a reduction factor of 0.4。
2. Calculation basis for pull-out force design values
2.1 Core regulatory basis
The calculation of chemical anchor pull-out force design values is mainly based on JGJ 145-2013 Technical Specification for Post-Installed Anchoring in Concrete Structures and GB/T 3098.1-2010 Mechanical Properties of Fasteners — Bolts, Screws and Studs. The former provides detailed provisions on tensile load capacity calculation for chemical anchors, tension internal force calculation for anchor groups, and characteristic bond strength values; the latter specifies the mechanical property classes of bolt materials and the corresponding strength indicators.
Per Clause 6.2.1 of JGJ 145-2013, the tensile load capacity of chemical anchors should comply with the following provisions:
The design tensile load capacity of a single anchor should be calculated separately for failure modes including anchor steel failure, concrete cone failure, and mixed failure, taking the minimum value among them
A base concrete strength class of at least C25 is a basic condition for chemical anchors to function properly
The ambient temperature during ordinary chemical anchor installation should be at least 10°C
Per GB/T 3098.1-2010, the designation system for bolt property classes consists of two numbers separated by a dot: the left number is the nominal tensile strength divided by 100, and the right number is 10 times the yield strength ratio. For example, class 8.8 denotes a nominal tensile strength of 800MPa and a yield ratio of 0.8.
2.2 Failure modes and load capacity values
The failure mode of a chemical anchor directly determines how the load capacity value is taken:
Steel failure: the anchor rod is pulled apart; the load capacity is taken as the design strength of the anchor steel. Per GB/T 3098.1-2010, the minimum tensile strength is 520MPa for class 5.8 and 800MPa for class 8.8
Concrete cone failure: the anchor pulls out a concrete cone; the load capacity is taken as the concrete cone failure capacity
Mixed failure: failure occurs at the adhesive-concrete interface; the load capacity is taken as the bond strength controlled value
For a conventional M12×160 property class 5.8 chemical anchor, per Table 4 of GB/T 3098.1-2010, its minimum tensile load is 43.8kN. With standard installation, the pull-out force can reach over 60kN, with a failure mode of rod tensile rupture, which is the ideal steel failure mode.
3. Chemical anchor pull-out testing standards
3.1 Main standards for testing
Chemical anchor pull-out testing is mainly based on the following standards:
JGJ 145-2013Technical Specification for Post-Installed Anchoring in Concrete Structures — Annex B "Test methods for chemical anchors for concrete"
GB 50550-2010Code for Acceptance of Construction Quality of Strengthening Works of Building Structures
GB 50367-2013Design Code for Strengthening of Concrete Structures
GB/T 3098.1-2010Mechanical Properties of Fasteners — Bolts, Screws and Studs — mechanical property benchmark for anchor materials
Annex B of JGJ 145-2013 explicitly stipulates that the installation performance of chemical anchors should be tested in tension using C25 concrete。
3.2 Sampling requirements for on-site pull-out tests
Per GB 50550-2010 and JGJ 145-2013, sampling for on-site pull-out tests should meet the following requirements:
Inspection batch division: anchors of the same type, size, and strength class installed on the same type of member with basically identical anchoring locations form one inspection batch
Sample quantity: take 1‰ of the total number of anchors in each inspection batch, and no fewer than 5 pieces for inspection
Sampling locations: choose locations that are easy to repair and re-anchor
Curtain wall projects: every 1,000 anchors form one inspection batch (fewer than 1,000 counted as one batch), with a random sample of 1‰ and no fewer than 5 anchors
3.3 Acceptance criteria for pull-out tests
Per JGJ 145-2013 and related standards, the acceptance criteria for chemical anchor pull-out tests are as follows:
Load capacity requirement: the measured tensile load capacity should be no less than 1.5 times the design load
Load holding stability: during load holding, the load indication of the loading device should decrease by no more than 5% within 2 minutes, with no slip of the anchor and no cracks or other signs of local damage in the base concrete
Failure mode: the ideal failure mode is concrete cone failure or mixed failure of the base material; anchor pull-out or adhesive fracture indicates a fail
Minimum standard: the measured load capacity should not be lower than 90% of the anchor product's standard value
For an M12 chemical anchor with a design tension of 19.8kN, the measured value in the on-site pull-out test should be no less than 29.7kN (19.8 × 1.5), with no slip and no cracks during 2 minutes of load holding, to be judged as passing.
4. Impact of construction quality on pull-out force
4.1 Hole cleaning is the key determinant of pull-out force
The pull-out force of a chemical anchor depends not only on the product itself but also on construction quality. Among all factors, hole cleaning and dust blowing is the most critical step.
Taking a conventional M12×160 property class 5.8 chemical anchor as an example:
Standard installation (three brushing and three blowing cycles): pull-out force can reach 50-60kN
Blowing only, without brushing the hole: pull-out force of about over 40kN
No hole cleaning at all: pull-out force loses about half, leaving only about 25kN
Daring's recommended hole cleaning procedure is: (1) after drilling, use a dust blower to remove most of the dust; (2) clean the dust from the hole wall with a rotary brush; (3) blow again with the dust blower until no visible dust escapes from the hole. With this cleaning, the pull-out force of an M12×160 chemical anchor can generally reach 50-60kN.
4.2 Design safety factor
The load capacity of Daring chemical anchors at standard embedment depth often exceeds the design value by 3-5 times, demonstrating commendable safety. For an M30 chemical anchor, per GB/T 3098.1-2010, the minimum tensile load of a property class 8.8 M30 bolt reaches 466kN, far exceeding actual design loads, with ample safety margin.
Daring chemical anchors have passed the high-temperature resistance test of the National Building Materials Testing Center. Paired with chemical anchor ampoules, they cure quickly within 1 hour with no diluters added, maximizing chemical anchor performance.
5. Selection and application recommendations
5.1 Selection reference for different scenarios
| Application scenario | Recommended size | Recommended property class | Minimum tensile load (kN) | Remarks |
|---|---|---|---|---|
| Light-load equipment fixing, piping installation | M8-M10 | Class 5.8 | 19.0-30.2 | Non-load-bearing structures |
| Curtain wall framing, steel structure connections | M12-M16 | Class 5.8 or 8.8 | 43.8-125.0 | Non-load-bearing or auxiliary load-bearing |
| Heavy equipment, high-load connections | M20-M24 | Class 8.8 | 203.0-293.0 | Must meet standard requirements |
| Load-bearing structures (special reverse-cone) | Reverse-cone chemical anchor | Class 8.8 | Use values from the product report | Must comply with JGJ 145-2013 |
5.2 Selection precautions
Load-bearing structures must use special reverse-cone chemical anchors: ordinary chemical anchors are strictly prohibited in load-bearing structures and cracked concrete
Design values should follow the product test report: the data in the table above are standard reference values; actual design values should follow the product test report and structural design drawings
On-site pull-out testing is an essential step of quality acceptance: after the adhesive has fully cured, sampled on-site pull-out load capacity inspection should be performed
Daring can provide load capacity reports: Daring chemical anchors have passed high-temperature welding tests, and Daring can provide purchasers with corresponding load capacity reports and material analysis reports
6. Frequently asked questions
| Q1 | What is the design pull-out force value of an M12 chemical anchor? Per Table 4 of GB/T 3098.1-2010, the minimum tensile load of an M12×160 property class 5.8 chemical anchor is 43.8kN. With standard installation, Daring M12 chemical anchors achieve a pull-out force of over 60kN. |
| Q2 | What are the acceptance criteria for chemical anchor pull-out tests? Per JGJ 145-2013, the measured tensile load capacity should be no less than 1.5 times the design value, the load drop during 2 minutes of load holding should not exceed 5%, and the anchor should show no slip and the base material no cracks. |
| Q3 | What is the sampling ratio for on-site pull-out tests? Per GB 50550-2010, take 1‰ of the total number of anchors in each inspection batch, and no fewer than 5 pieces. For curtain wall projects, every 1,000 anchors form one inspection batch, with 1‰ sampled and no fewer than 5 anchors. |
| Q4 | How much does failure to clean the hole affect pull-out force? For an M12×160 chemical anchor, the pull-out force can reach 50-60kN with standard installation, while complete failure to clean the hole cuts the pull-out force roughly in half, leaving only about 25kN. Hole cleaning is the key to ensuring pull-out force. |
| Q5 | What pull-out force can Daring chemical anchors achieve? Daring M12 chemical anchors achieve a pull-out force of over 60kN. Per GB/T 3098.1-2010, the minimum tensile load of a property class 8.8 M30 bolt is 466kN, far exceeding design values, with ample safety margin. |
The Daring chemical anchor range covers high-strength, capsule, special reverse-cone, and dynamic-load reverse-cone anchors, in materials including class 5.8 and 8.8 carbon steel (hot-dip galvanized ≥45μm) and 304/316 stainless steel, produced strictly in accordance with GB/T 3098.1-2010 and JGJ 145-2013. Paired with Daring DL-200E modified epoxy injection anchoring adhesive that meets the national Class A adhesive standard, the anchors offer strong bonding and anchoring force, temperature resistance, seismic performance, and compatibility with cracked concrete. Daring can provide corresponding load capacity reports and material analysis reports. For advice on pull-out force design value calculation or testing plans for a specific project, please contact the Daring technical team.
References
Daring official website — High-strength chemical anchor product parameters
Daring official website — Impact of hole cleaning and dust blowing on chemical anchor performance
Daring official website — Daring chemical anchor project gallery
GB/T 3098.1-2010 Mechanical Properties of Fasteners — Bolts, Screws and Studs — mechanical property classes of threaded fasteners
JGJ 145-2013 Technical Specification for Post-Installed Anchoring in Concrete Structures — chemical anchor design and testing
GB 50550-2010 Code for Acceptance of Construction Quality of Strengthening Works of Building Structures — on-site pull-out inspection
GB 50367-2013 Design Code for Strengthening of Concrete Structures — anchor selection for load-bearing structures