How much load capacity difference is there between M8 and M6 back bolts? A complete selection guide

Views: 0Posted on: 2026-08-11

Conclusion first:Under the same working conditions, the pull-out load capacity of an M8 back bolt is about20%, with the design steel load capacity higher by about80%. Specific selection requires comprehensive judgment based on panel thickness, stone type and project conditions.

In stone curtain wall projects, back bolt selection directly affects the safety of the entire curtain wall system. Many designers and engineers face a practical question: both are back bolts, so how much difference is there really between M6 and M8, and which should be chosen for a project? This article gives a direct answer based on measured data and design codes.

I. How big is the capacity difference? Look at the data

Data 1: design values of steel load capacity (code requirements)

According to general back bolt design requirements, clear provisions apply to the design tensile load capacity of back bolt steel:

SizeDesign value of tensile load capacityDesign value of shear load capacity
M6 ≥11.5 kN ≥6.4 kN
M8 ≥20.9 kN ≥11.9 kN

The design tensile load capacity of M8 is1.82 times that of M6, and the design shear load capacity is1.86 times。

Data 2: pull-out tests on stone base material (comparison under the same conditions)

Pull-out test data from TÜV Rheinland (Germany) on 40 mm thick granite show that:

SpecificationAverage of three tests
M6 anti-loosening back boltapproximately 11.5 kN
M8 anti-loosening back boltapproximately 14.0 kN

The pull-out force of M8 is about 20% greater than M6, a relatively noticeable improvement in load capacity.

Data 3: comparison of different back bolt types

Even for the same M6 size, back bolts with different structures differ in load capacity. Under the same base material and embedment depth, the tensile force of an anti-loosening back bolt isabout 15% higherthan that of a screw-in back bolt. This shows that:choosing the right model is as important as choosing the right size.

II. Why does M8 have a higher load capacity than M6?

The fundamental reason for the capacity difference lies in thecontact area. The tensile force of a stone back bolt is proportional to the base material strength, embedment depth and contact area at the bottom of the bolt. An M8 back bolt has a larger shank diameter (8 mm vs 6 mm) and a larger undercut diameter (about 11.5 mm vs 9.5 mm), giving a larger contact area with the stone and therefore higher anchorage force. However, one point deserves special attention:load capacity depends not only on size but also on embedment depth. Under the same base material and embedment conditions, M8 has a higher capacity than M6; but if the M6 embedment is much greater than that of M8, the result may be reversed.

III. Selection guide: when to use M6 and when to use M8?

(I) Selection by panel thickness

The primary basis for back bolt selection ispanel thickness. The embedment depth of a back bolt should be1/2 to 2/3of the panel thickness. For double-cut back bolts, the remaining thickness from the bottom of the hole to the panel surface must not be less than 6 mm; for other types of back bolts it must not be less than 10 mm.

Panel thicknessRecommended back bolt sizeReference embedment depth
8-20mm M6 5-12mm
20-25mm M6 or M8 (depending on load) 12-15mm
25-35mm M8 15-21mm
Above 35 mmM8Above 21 mm

Under normal circumstances,M8 back bolts are recommended for stone thicker than 35 mm. M6 back bolts suit panels 8-20 mm thick, while M8 suits panels 20-40 mm thick.

(II) Selection by stone type

Different stone types have different requirements for back bolts:

  • soft stone(marble, sandstone, limestone, etc.): test results on various soft stones show thatM8 back bolts have a far higher load capacity than M6, therefore soft stone projectsshould use M8 back bolts。

  • Hard stone(granite, etc.): both M6 and M8 can be used, determined by calculation based on thickness and load.

(III) Selection by project conditions

Under the following conditionsM8 back bolts are recommended:

  • Stone panels larger than 1.5 m²

  • Single panel weighing more than 100 kg

  • Stone installation height exceeding 50 m

  • High seismic design requirements (e.g., 8-degree zones)

  • Coastal areas with high wind pressure

(IV) Selection by back bolt type

In addition to the M6/M8 size choice, the type of back bolt itself also affects load capacity:

Back bolt typeApplicable panel thicknessFeatures
Screw-in back bolt10-20 mm thin panelsInstalled by screwing in; requires high drilling accuracy
Hammer-in back boltThick panels above 25 mmMarket share above 80%, high cost-effectiveness
Anti-loosening back boltMedium-thick panels above 16 mmUnique anti-loosening effect, first choice for soft stone

The hammer-in back bolt is currently the most widely used back bolt for stone dry-hung cladding; it costs less than the screw-in type and offers relatively good safety and cost-effectiveness.

IV. Correct method for load capacity calculation

When selecting back bolts, designers cannot rely on experience alone; load capacity verification is also required. The design load capacity of a back bolt should be taken as theminimum。

of the calculated values for the following failure modes:

The shank itself is pulled apart; this is independent of embedment depth and depends only on the effective cross-sectional area and steel strength.

NRd,s = As × fuk / γMsWhere:
As = effective stress area of the shank (about 20.1 mm² for M6, about 36.6 mm² for M8)
fuk = characteristic ultimate tensile strength of steel (700 MPa for A2-70, 800 MPa for A4-80)
γMs = partial factor for steel, taken per clause 4.3.10 of JGJ 145-20131.2~1.3

Taking M6, A2-70 as an example (γMs = 1.25):
NRd,s = 20.1 × 700 / 1.25 ≈ 11.26 kN

This estimated value is basically consistent with the code value of design tensile capacity ≥11.5 kN for M6.

Note:Back bolt shanks often use special threads; As should be based on the effective area provided by the manufacturer.

(II) Concrete cone failure (base material pulled out)

When embedment depth is insufficient, an inverted cone of base material may be pulled out as a whole. The load capacity depends onbase material strengthandembedment depth, and is independent of steel strength.

NRd,c = NRk,c / γMc
NRk,c = 7.0 × √fcu,k × heff1.5Where:
fcu,k = standard value of concrete cube compressive strength (for C30 concrete, take 30 MPa)
heff = effective embedment depth (mm)
γMc = partial factor for concrete, taken per JGJ 145-2013 as1.8(non-seismic) or2.0(seismic)

The above are ideal values for a single anchor without edge effects or cracks. In actual design, NRk,c must be multiplied by the following correction factors:

  • ψs,N = edge distance correction factor (capacity decreases when the anchor is close to an edge)
  • ψre,N = crack correction factor (capacity is reduced when the base material is cracked)
  • ψec,N = group anchor correction factor (under group anchor effects, capacity is not simply additive)

(III) Splitting failure (thin panels or small edge distance)

When the base material is thin (h < 2heff) or the anchor is close to an edge (c < 1.5heff), splitting failure may occur. This is a control mode in back bolt selection that iseasily overlooked but critical.

NRd,sp = NRk,sp / γMc
NRk,sp = ksp × NRk,cWhere:
ksp = splitting influence factor (taken per clause 6.1.9 of JGJ 145-2013)
NRk,c = characteristic value of concrete cone failure capacity (calculated with the same formula above)
γMc = partial factor for concrete, taken as 1.8

Judgment condition:When edge distance c < 1.5heff or panel thickness h < 2heff,splitting failure must be verified。

(IV) Bond failure (applicable to chemical anchors, not to back bolts)

Bond failure is a failure mode exclusive to chemical anchors and applies to adhesive anchoring systems such as chemical anchors and post-installed rebar. For back bolts (undercut mechanical anchors), anchorage force comes from themechanical interlockof the undercut hole and expansion segment at the base, not the bond strength of adhesive, thereforebond failure is not included in back bolt selection verification。

Under normal installation conditions, back bolts do not experience bond failure. Only in extreme cases such as oil stains or uncleaned dust in the hole may pull-out occur due to friction loss; such cases should be classified as construction quality problems and are not design failure modes specified in the codes.

Note:Bond failure applies only to chemical anchors. A back bolt is a mechanical anchor (undercut type); its anchorage force comes from the mechanical interlock of the undercut hole and expansion segment at the base, not the bond strength of adhesive. The bond failure formula does not apply to back bolts.Core principle:The design load capacity of a back bolt is taken as thesteel failure、concrete cone failure、splitting failuretheminimum. In actual engineering, themeasured values in product test reportsandon-site pull-out test resultsas the basis; theoretical calculations serve only as design references. Formal design must be carried out in accordance withJGJ 145-2013, Technical Specification for Post-Installed Anchorage of Concrete Structures.

Beijing local standard requirements

Beijing local standards stipulate that when back bolts are used to connect stone cladding panels, back bolt tensile design must be performed, andthe ultimate tensile capacity of a single threaded rod after bonding to stone must not be less than 3.2 kN. This is the minimum threshold that must be met during selection.

V. Comparison of key installation parameters

Parameter M6 M8
Drilling diameter (D1) Ф7.2mm Ф9.5mm
Undercut diameter (D2) Ф9.5±0.3mm Ф11.5±0.3mm
Common embedment depth 5、7、9、12、15mm 15、18、20mm
Applicable panel thickness 8-20mm 20-40mm

Drilling accuracy directly affects the anchoring performance of back bolts. If hole diameter deviation exceeds the allowable range, anchoring failure will result.

VI. Frequently asked questions

Q1 Is the load capacity of an M8 back bolt always twice that of an M6?
A Not necessarily. In terms of design steel load capacity, M8 is about 1.8 times M6; but in pull-out tests on stone base material, M8 is about 20% higher than M6. The specific difference depends on multiple factors including base material strength, embedment depth and back bolt type.
Q2 Can M8 back bolts be used on 20 mm thick stone?
A Yes, but special attention must be paid to embedment depth. For a 20 mm panel, the embedment depth should be 10-13 mm, while the minimum embedment of an M8 back bolt is usually 15 mm, which may exceed the requirement of half the panel thickness. It is recommended to prefer M6 back bolts on 20 mm panels, or to select custom M8 back bolts with a shallower embedment.
Q3 Can M6 back bolts meet the requirements of high-rise curtain walls?
A It depends on the specific load conditions. For curtain walls of ordinary height with conventional panel sizes, M6 back bolts in a reasonable quantity (4-6 per panel) can meet requirements. However, for projects with installation heights exceeding 50 m or high wind pressure, upgrading to M8 back bolts is recommended.
Q4 Why must M8 be used for soft stone?
A Soft stones such as marble and sandstone have low inherent strength, and M6 back bolts have a small contact area with the stone, making pull-out failure likely. Tests show that the load capacity of M8 on soft stone is far higher than M6.
Q5 How is the number of back bolts determined?
A Four back bolts are typically used on standard panels, while large panels require six. In actual installation, two back bolts usually carry more load, so selection should be calculated under the most unfavorable loading condition.

VII. Selection decision flowchart

Start │ ▼ Measure stone thickness │ ▼ Panel thickness ≤20 mm? ─── Yes ──→ Select M6 back bolt │ No ▼ Panel thickness 20-35 mm? │ ├── Yes ──→ Calculate load │ │ │ ├── Low load, low height ──→ M6 acceptable │ └── High load, high height ──→ Select M8 │ No (>35 mm) ▼ Select M8 back bolt │ ▼ Determine stone type │ ├── Soft stone (marble, sandstone, etc.) ──→ M8 required └── Hard stone (granite, etc.) ────────→ M6 or M8 acceptable │ ▼ Determine back bolt type (hammer-in / screw-in / anti-loosening) │ ▼ Verify load capacity (design value ≥ load effect) │ ▼ Verify by on-site pull-out test │ ▼ Selection complete

VIII. Summary

Comparison dimensionM6 back boltM8 back bolt
Design tensile load capacity ≥11.5kN ≥20.9kN
Design shear load capacity ≥6.4kN ≥11.9kN
Applicable panel thickness 8-20mm 20-40mm
Recommended applicationsStandard curtain walls, small-format panelsHigh-rise curtain walls, large-format panels, soft stone
PriceLowerHigher

Core selection principles:

  1. Thickness first: use M6 below 20 mm, M8 above 35 mm, and calculate by load in the intermediate range.

  2. Use M8 directly for soft stone: do not use M6 on soft stone to save costs.

  3. Use M8 directly for high-rise, high wind pressure and large panels: safety redundancy is essential.

  4. Load capacity must be verified: judgment cannot be based on experience alone; capacity calculations must follow the codes.

  5. Verify by on-site pull-out test: after theoretical calculation, pull-out tests should be carried out on the actual stone of the project for confirmation.

Daring offers the full M6 and M8 back bolt range, covering hammer-in, screw-in and anti-loosening types, and can provide custom embedment solutions to project requirements. For back bolt selection calculations for specific projects, please consult the Daring technical team.

References

1. General design requirements for back bolts — design tensile load capacity of steel: M6 ≥ 11.5 kN, M8 ≥ 20.9 kN (general industry design standard)

2. TÜV Rheinland pull-out test — M8 back bolt pull-out force about 20% greater than M6 (third-party test report)

3. Daring website— back bolt technical parameters and installation specifications

4. Technical Specification for Post-Installed Anchorage of Concrete Structures, JGJ 145-2013(national standard)

5. Beijing local standard — ultimate tensile capacity of back bolts not less than 3.2 kN (local standard)

6. Back bolt embedment depth — 1/2 to 2/3 of panel thickness (general industry design principle)